Allen-Bradley 1757-ABRIO User Manual
Allen-Bradley 1757-ABRIO User Manual

Allen-Bradley 1757-ABRIO User Manual

Process remote i/o rio communication interface module
Hide thumbs Also See for 1757-ABRIO:
Table of Contents

Advertisement

Process Remote I/O
(RIO)
Communication
Interface Module
1757-ABRIO
User Manual
Allen-Bradley HMIs

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the 1757-ABRIO and is the answer not in the manual?

Questions and answers

Summary of Contents for Allen-Bradley 1757-ABRIO

  • Page 1 Process Remote I/O (RIO) Communication Interface Module 1757-ABRIO User Manual Allen-Bradley HMIs...
  • Page 2: Important User Information

    In no event will Allen-Bradley be responsible or liable for indirect or consequential damage resulting from the use or application of these products.
  • Page 3: Your Questions Or Comments On This Manual

    1. Go to http://www.ab.com 2. Click on Product Support (http://support.automation.rockwell.com) Your Questions or Comments on this Manual If you find a problem with this manual, please notify us of it on the enclosed How Are We Doing? form. Allen-Bradley HMIs...
  • Page 4 Notes:...
  • Page 5: Table Of Contents

    Overview 1757-ABRIO ........1-1 Mapping and Accessing RIO Data ....1-2 RSLinx Requirements.
  • Page 6 Chapter 4 Monitoring the 1757-ABRIO Overview ........4-1 Monitoring Discrete I/O .
  • Page 7 Configuring the Hart Network ....5-32 Hart Command status......5-37 Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 8 Normal Operational Messages ..... . B-1 Exception Handling Messages ..... . B-4 the 1757-ABRIO and PLC-5 Appendix C...
  • Page 9: Preface

    See Table 5.2 on page 5-1 for a listing of related ControlLogix documentation: If you need more information on these products, contact your local Allen-Bradley integrator or sales office for assistance. For more information on the documentation, refer to the Allen-Bradley Publication Index, publication SD499 or visit us at: •...
  • Page 10 Preface Notes: Publication 1757-UM007A-EN-P - April 2002...
  • Page 11: Overview

    Chapter Overview 1757-ABRIO This document is a user guide for the 1757-ABRIO module, which allows Rockwell Automation controllers (ProcessLogix or ControlLogix) to communicate with Allen-Bradley 1771 RIO. The module acts as a RIO scanner. This module was developed to facilitate connection to existing analog RIO devices from Logix-based processors.
  • Page 12: Mapping And Accessing Rio Data

    RIO Data host processor reads or writes using unscheduled messages. You map data that the module receives or sends into these tags. The data mapping is stored in flash memory on the 1757-ABRIO module. 1757-ABRIO Module Write Data From CLX/PLX...
  • Page 13: Rslinx Requirements

    RSLinx 3.31 or above. Installing AbRioCfg 1. RSLinx should be installed before you install the AbRioCfg software. 2. Insert the CD supplied with the 1757-ABRIO and run the program setup.exe. Messages about DTL32.DLL during installation or IMPORTANT when you run the program indicate problems with the RSLinx installation.
  • Page 14 Overview If you see question marks for the 1757-ABRIO module when running RSNetWorx or RSLinx, install the EDS file from the CD. You do not need to load the firmware on the CD into your 1757-ABRIO module as the module ships with the latest version of firmware.
  • Page 15: Quick Start

    2-10. file. 6. Download the Downloading the Configuration configuration to on page 2-11. 1757-ABRIO module. 7. Create your application to Accessing Data on the access data on the module. 1757-ABRIO on page 3-1. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 16 Overview Notes: Publication 1757-UM007A-EN-P - April 2002...
  • Page 17: Configuring The 1757-Abrio

    Autoconfiguring I/O Racks The first step in building a configuration is to perform an autoconfiguration. The RIO network must be connected to the 1757-ABRIO module and the module must be in “inactive” mode. When using AbRioCfg, you must left click to ATTENTION select/highlight before you can right click to activate menu options.
  • Page 18 All of the racks on one RIO network must operate at the same baud rate. The 1757-ABRIO then sends messages to all possible racks and builds the network rack configuration from the responses. It displays a list of the racks it found in the network tree.
  • Page 19 Configuring the 1757-ABRIO The 1757-ABRIO has been designed to provide fault responses similar to the PLC-5 as well as the PLX and CLX. This provides consistency when integrating existing I/O with new controllers. 6. Right click on each rack in the network tree and select Enter Rack Switch Setting from the menu.
  • Page 20: Adding Block Transfer Modules

    Configuring the 1757-ABRIO This setting tells the 1757-ABRIO what to do if the host processor stops updating the tag that this rack’s discrete data is mapped to. Adding Block Transfer Autoconfiguration can locate the racks present on the network but it cannot detect the I/O modules in those racks.
  • Page 21: Addressing Modes

    Configuring the 1757-ABRIO Addressing Modes Allen-Bradley 1771 racks have three addressing modes - 1/2-slot, 1-slot and 2-slot addressing. The addressing mode is set by switches in the backplane of the chassis and is set on a per-chassis basis. The addressing mode determines how physical block transfer modules map into logical addresses (rack, I/O group and slot).
  • Page 22: Configuring Block Transfer Modules

    The 1757-ABRIO performs scaling between raw I/O data and floating point user values. You send floating point output values to the 1757-ABRIO which it then converts to raw output values using the scaling values you supplied in the configuration. Similarly, the 1757-ABRIO converts raw input data to floating point values, using the scaling you enter.
  • Page 23: Input Scaling

    Configuring the 1757-ABRIO Input Scaling For analog input modules, you supply the floating point values you want the minimum and maximum raw data scaled to. • minimum corresponds to the lowest raw value • maximum corresponds to the maximum raw value...
  • Page 24: Creating Tags

    Before you program the PLX or CLX to read or write to the 1757-ABRIO, you must define the Tags in AbRioCfg. The 1757-ABRIO supports five types of tags. Numeric Read and Numeric Write •...
  • Page 25: Creating A Tag

    The range of values is 100 to 15000 ms. The default is 5000 ms. If the tag time-out is exceeded, the tag times out and the 1757-ABRIO takes appropriate action. 5. Click OK to accept the tag. You can create a maximum of 64 tags, of any combination of types.
  • Page 26: Mapping Data To Tags

    2-10 Configuring the 1757-ABRIO Mapping Data to Tags You map discrete I/O and block transfer modules differently. Discrete I/O When mapping Discrete I/O with flags, drag the I/O Grp 1-7 from the network tree to the location in the tag where you want the data to be located.
  • Page 27: Deleting Mapped Data

    Uploading a Configuration You can upload a configuration from a 1757-ABRIO module using the Actions => Upload config command from the menu or using the Upload Config From Module button on the toolbar.
  • Page 28 2-12 Configuring the 1757-ABRIO Notes: Publication 1757-UM007A-EN-P - April 2002...
  • Page 29: Accessing Data On The 1757-Abrio

    Chapter Accessing Data on the 1757-ABRIO Overview This chapter describes the operating modes of the 1757-ABRIO and describes how to access data on the module from a ProcessLogix or ControlLogix processor, or using OPC/DDE. Modes of Operation There are four modes of operation for the module.
  • Page 30: Active Mode (Run)

    Accessing Data on the 1757-ABRIO When the module is in INACTIVE mode, the RIO network is placed in program mode with input updates but no output updates. The 1757-ABRIO module must be in the Inactive Mode to accept a download. ACTIVE Mode (Run) The module is in ACTIVE mode when it receives a message from either a host processor or from an OPC or DDE server.
  • Page 31: Processlogix Accessing Data From The Abrio

    Accessing Data on the 1757-ABRIO ProcessLogix Accessing To access tag data on the 1757-ABRIO from a ProcessLogix controller, you use REQNUMARRAY, REQFLAGARRAY and REQTEXTARRAY Data from the ABRIO Exchange Blocks with CIPREAD and CIPWRITE commands to read and write tags.
  • Page 32 Accessing Data on the 1757-ABRIO 7. Set the number of values to be read or written. a. flag arrays, 512 max b. numeric arrays, 64 max c. text arrays, 64 max Figure 3.1 Array Examples Text Arrays Numeric Arrays Flag Arrays 8.
  • Page 33 Accessing Data on the 1757-ABRIO 10. Set the Path from the PLX to the 1757-ABRIO. Refer to Identifying the Path on page 3-11 or ControlBuilder Help for information on entering the path. 11. Set the FileName in the Exchange Blocks to the names of the tags you created in the 1757-ABRIO.
  • Page 34: Controllogix Accessing Data From The Abrio

    Accessing Data on the 1757-ABRIO ControlLogix Accessing There are several tasks you need to complete before you can access data from ControlLogix. You need to create: Data from the ABRIO • Tags for messages • Tags for storage areas • Message commands to read RIO data •...
  • Page 35: Second: Create Message Commands To Read And Write All Rio Data

    2-8 for more information. Table 3.1 shows the source (write) or destination (read) data type to use with each 1757-ABRIO tag type and the size for each type. Table 3.1 ControlLogix Data types 1757-ABRIO tag Source/destination type Storage Data Size...
  • Page 36 2. Select the Message Type. The Message type should be either CIP Data Table Read to read a tag from the 1757-ABRIO or CIP Data Table Write to write a tag to the 1757-ABRIO. 3. Select the Source Element.
  • Page 37 Tag Name that is listed under Numeric Read Tags. If you are writing to a tag on the 1757-ABRIO, this is the 1757-ABRIO tag name. If you are reading a tag from the 1757-ABRIO, this is When you read the ControlLogix tag name.
  • Page 38 3-10 Accessing Data on the 1757-ABRIO You must tell RSLogix the path to the ABRIO module. The ABRIO, PLX and CLX most likely will not be in the same racks so the path might be a bit complicated to figure out.
  • Page 39: Identifying The Path

    Accessing Data on the 1757-ABRIO 3-11 Identifying the Path Here is a general example of how to find the path to the rack you need to map to: Illustrated is the path from the PLX or the CLX to the remote ABRIO module.
  • Page 40: Accessing Data From Opc/Dde

    Enter the Path here. 8. Click OK to accept the MSG instruction. Accessing Data from You can access data on the 1757-ABRIO directly using a DDE or OPC server such as RSLinx, without the intervention of a host processor. OPC/DDE...
  • Page 41: Accessing The Data

    11. Change Local or Remote Addressing defaults to Local. If you are using a bridge device to communicate with the 1757-ABRIO, select Remote and configure the bridging. Refer to the RSLinx documentation for detailed information on how to configure bridging.
  • Page 42 3-14 Accessing Data on the 1757-ABRIO 1. Try sending data to and reading data from a 1771-SIM module or an I/O module that you have inputs connected. 2. Put CLX in Program Mode. The ABRIO will go Inactive. 3. Put ABRIO in Forced Active Mode.
  • Page 43: Monitoring The 1757-Abrio

    Chapter Monitoring the 1757-ABRIO Overview The AbRioCfg utility lets you monitor the operation of the module and perform maintenance operations. Tag, block transfer, and module diagnostic counters are available only from AbRioCfg, and are not available to a PLX/CLX processor.
  • Page 44: Monitoring The Data Value Of Tags

    If you attempt to monitor a tag that has not been downloaded to the 1757-ABRIO, AbRioCfg displays a message that indicates there is a configuration mismatch between the configuration in AbRioCfg and the configuration in the 1757-ABRIO.
  • Page 45: Monitoring The Status Of A Block Transfer

    Monitoring the 1757-ABRIO Use the same procedure to monitor discrete and text data. Monitoring the Status of a To monitor the current status of a block transfer: Block Transfer 1. Left click on the next to the rack where the block transfer module you want to monitor is located.
  • Page 46: Monitoring The Scanner Log

    Monitoring the Scanner Log The scanner log displays messages from the firmware running on the 1757-ABRIO, showing its normal operation and error messages. It may be useful in tracking down errors and for Technical Support. To monitor the scanner log, select Tools => Monitor Scanner Log.
  • Page 47: Monitoring Diagnostic Counters

    This counter increments each time the 1757-ABRIO transmits a packet. RxGood This counter increments when the 1757-ABRIO receives a good packet. RxTout This counter increments when the 1757-ABRIO sends a packet but does not receive a reply. RxBadCRC This counter increments when the 1757-ABRIO receives a packet with a bad CRC.
  • Page 48: Fatal Errors

    This counter increments when the 1757-ABRIO receives a packet with a bad CRC from this rack. Tout This counter increments when the 1757-ABRIO sends a packet to this rack and does not receive a reply within the time-out period. Prtcl This counter increments when the 1757-ABRIO receives a packet from this rack that does not make sense in terms of the protocol.
  • Page 49: Overview

    The AbRioCfg utility takes care of the details of the module configuration using the parameters you supply. For applicable modules, the 1757-ABRIO scales the raw data to floating point values using optimal data resolution on the I/O module. Refer to the following publications for information on installing and using the supported modules.
  • Page 50: 1771-Ife

    Supported 1771 Modules Table 5.2 I/O Module Documentation Module Installation User Manual 1771-NOV 1771-6.5.127 1771-NR 1771-6.5.127 1770-HT1 1770-6.5.19 1771-IFE The 1771-IFE is a 12 bit analog input module that can be configured as 16 single-ended inputs or 8 differential inputs. Each channel can be configured as one of: Table 5.3 IFE Channel Configurations 1 to 5 VDC...
  • Page 51 0 to 5 VDC, an input of 0 VDC produces a scaled input value of 10.0 and an input of 5 VDC produces a scaled input of 22.5. The range of scaling values is -3.4e38 to 3.4e38. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 52: I/O Data

    Supported 1771 Modules 3. If desired, enable digital filtering and set the digital filtering time constant. If digital filtering is enabled, it applies to all channels. The digital filtering time constant can range from 0.01 to .99 seconds. 4. If desired, enable real-time sampling. If enabled, it sets the sampling rate for the data and overrides the Update Time.
  • Page 53: Diagnostic Data

    Channel 10 underrange Channel 11 underrange Channel 12 underrange Channel 13 underrange Channel 14 underrange Channel 15 underrange Channel 16 underrange Channel 1 overrange Channel 2 overrange Channel 3 overrange Allen-Bradley HMIs Channel 4 overrange Publication 1757-UM007A-EN-P - April 2002...
  • Page 54: 1771-Ofe

    Channel 14 overrange Channel 15 overrange Channel 16 overrange The Good Communication bit is set when the 1757-ABRIO is successfully communicating with the 1771-IFE module, and is 0 otherwise. The underrange and overrange bits are set when the raw input for a channel is outside the configured voltage or current range.
  • Page 55 3. Set the LAST STATE jumper setting to match the jumpers on the 1771-OFE module. The setting can be one of Last, Min, Mid or Max. This value determines how the 1757-ABRIO responds to a loss of communication with the host processor. 4. Set the Update Time.
  • Page 56: I/O Data

    Channel 1 data invalid bit Channel 2 data invalid bit Channel 3 data invalid bit Channel 4 data invalid bit The good communication bit is set if the 1757-ABRIO is successfully communicating with the 1771-OFE module. Publication 1757-UM007A-EN-P - April 2002...
  • Page 57: 1771-Ir

    When you add a 1771-IR module to a rack, the 1771-IR Module Dialog box appears. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 58 5-10 Supported 1771 Modules To configure the 1771-IR module: 1. Set the global RTD type to either 10-ohm copper or 100-ohm platinum. If the RTD you are using is neither of these two, you will override each channel to report the results in ohms. 2.
  • Page 59: I/O Data

    Channel 3 underrange Channel 4 underrange Channel 5 underrange Channel 6 underrange reserved Channel 1 overrange Channel 2 overrange Channel 3 overrange Channel 4 overrange Channel 5 overrange Channel 6 overrange reserved reserved Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 60: 1771-Ixe

    5-12 Supported 1771 Modules This data can be mapped to a flag read tag. 1771-IXE The 1771-IXE is an 8-channel thermocouple input module. The channels are configured in groups of four. The module supports types E, J, K, T, R and S thermocouples. The module can also be used as a millivolt input module.
  • Page 61: I/O Data

    Channel 2 data Channel 3 data Channel 4 data Channel 5 data Channel 6 data Channel 7 data Channel 8 data Cold junction temperature This data can be mapped to a numeric read tag. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 62: Diagnostic Data

    5-14 Supported 1771 Modules Diagnostic Data The 1771-IXE returns 24 bits of diagnostic data. Table 5.11 1771-IXE Diagnostic Data Description Module good communication Out of range RTS time-out reserved Low cold junction temperature High cold junction temperature reserved Calibration EEPROM failed Channel 1 underrange Channel 2 underrange Channel 3 underrange...
  • Page 63: Module Configuration

    • Optionally enabling real-time sampling and setting the sampling rate • Setting the update rate for the module block transfer read When you add a 1771-IL module to a rack, the 1771-IL Module dialog box appears. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 64 5-16 Supported 1771 Modules To configure the 1771-IL: 1. For each channel select the range for each channel and enter the scaling values. The low scaling value corresponds to the minimum input voltage or current; the high scaling value corresponds to the maximum voltage or current. For example, if the scaling values are 10.0 and 22.5 and the range is configured for 0 to 5 VDC, an input of 0 VDC produces a scaled input value of 10.0 and an input of 5 VDC produces a scaled input of 22.5.
  • Page 65: I/O Data

    The 1771-IL returns 24 bits of diagnostic data. Table 5.14 1771-IL Diagnostic Data Description Module good communication Out of range Invalid scaling (should never be set) RTS time-out Invalid filter reserved Hardware failure Allen-Bradley HMIs reserved Publication 1757-UM007A-EN-P - April 2002...
  • Page 66: 1771-Noc

    5-18 Supported 1771 Modules Table 5.14 1771-IL Diagnostic Data Description Channel 1 underrange Channel 2 underrange Channel 3 underrange Channel 4 underrange Channel 5 underrange Channel 6 underrange Channel 7 underrange Channel 8 underrange Channel 1 overrange Channel 2 overrange Channel 3 overrange Channel 4 overrange Channel 5 overrange...
  • Page 67 Minimum, Maximum, Last State or User Value. This is the value the channel output will be if the 1771-NOC loses communication with the 1757-ABRIO or the host processor stops updating the tag to which the 1771-NOC’s data is mapped. If the Reset State is set to User Value, you must also enter a reset value.
  • Page 68: I/O Data

    5-20 Supported 1771 Modules 5. Click OK to accept the module configuration. I/O Data The host application writes 8 words of floating point data to the 1771-NOC Table 5.15 1771-NOC I/O Data Word Description Channel 1 data Channel 2 data Channel 3 data Channel 4 data Channel 5 data...
  • Page 69: 1771-Nov

    • optionally enabling real-time sampling and setting the rate • setting the update time for the module’s block transfer write When you add a 1771-NOV module to a rack, the 1771-NOC(V) dialog box appears. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 70 Minimum, Maximum, Last State or User value. This is the value the channel output will be if the 1771-NOV loses communication with the 1757-ABRIO or the host processor stops updating the tag to which the 1771-NOV’s data is mapped. 3. If the Failure State for a channel is set to User Value, enter the User value.
  • Page 71: I/O Data

    This data can be mapped to a numeric write tag. Diagnostic Data The 1771-NOV returns 16 bits of diagnostic data. Table 5.18 1771-NOV Diagnostic Data Description Module good communication reserved reserved reserved reserved reserved Allen-Bradley HMIs reserved Publication 1757-UM007A-EN-P - April 2002...
  • Page 72: 1771-Niv

    5-24 Supported 1771 Modules Table 5.18 1771-NOV Diagnostic Data Description reserved Channel 1 data invalid Channel 2 data invalid Channel 3 data invalid Channel 4 data invalid Channel 5 data invalid Channel 6 data invalid Channel 7 data invalid Channel 8 data invalid This data can be mapped to a flag read tag.
  • Page 73 RIO network and whether block transfers are running to other modules in the same rack. 5. Click OK to accept the module configuration. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 74: I/O Data

    5-26 Supported 1771 Modules I/O Data The 1771-NIV returns 8 words of floating point data to the host processor. Table 5.19 1771-NIV I/O Data Word Description Channel 1 data Channel 2 data Channel 3 data Channel 4 data Channel 5 data Channel 6 data Channel 7 data Channel 8 data...
  • Page 75: 1771-Nr

    The 1771-NR module is an 8-channel RTD input module. It supports the following types of RTDs: • 100 ohm platinum US standard • 100 ohm platinum European standard • 10 ohm copper • 120 ohm nickel • ohms mode Allen-Bradley HMIs The module: Publication 1757-UM007A-EN-P - April 2002...
  • Page 76: Module Configuration

    5-28 Supported 1771 Modules • reports the temperature in degrees Fahrenheit or Celsius • supports digital filtering on any channel, with a time constant from 0.1 to 9.9 seconds. Module Configuration Configuring the 1771-NR consists of: • setting the RTD type for each channel. For 10 ohm copper RTDs, you can enter an offset at 25C.
  • Page 77: I/O Data

    Table 5.21 1771-NR I/O Data Data Word Description Channel 1 data Channel 2 data Channel 3 data Channel 4 data Channel 5 data Channel 6 data Channel 7 data Channel 8 data Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 78: Diagnostic Data

    5-30 Supported 1771 Modules This data can be mapped to a numeric read tag. Diagnostic Data The 1771-NR returns 40 bits of diagnostic data. Table 5.22 1771-NR Diagnostic Data Description Module good communication reserved reserved reserved reserved reserved reserved reserved Channel 1 bad calibration Channel 2 bad calibration Channel 3 bad calibration...
  • Page 79: 1770-Ht1

    • The 1757-ABRIO is intended to be used with Hart input devices. It is not suitable for use with output devices. Allen-Bradley HMIs...
  • Page 80: Rack Requirements

    2. Add the 1770-HT1 to the appropriate rack. The HT1 must be the only module in that rack. At this point, the 1757-ABRIO does not know how to complete the rest of the Hart configuration until it has the configuration with the 1770-HT1 included.
  • Page 81 Set the maximum address (range 0 to 15) to search on each channel. If you have one Hart device on each channel set Max Address to 1. 4. Click OK to start the search. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 82 5-34 Supported 1771 Modules The Hart Configuration program displays a progress bar as it searches the Hart network devices. When the search is complete, expand the Hart Config to display the devices found. To send a message to a device or add a cyclic command to a device: 1.
  • Page 83 If you have not already done so, create tags to accept the data from the Hart commands and map the 1770-HT1 module to those tags. The 1770-HT1 occupies an entire numeric read, flag read or text read tag. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 84 If it is correct, click Add Cyclic to have the data read repeatedly and attached to the ABRIO tag. 5. Save the configuration and download it to the 1757-ABRIO. Do not add write commands as cyclic commands...
  • Page 85: Hart Command Status

    Primary variable out of limits When you enter a flag offset when you create a cyclic command, this is what gets returned at that offset. Nothing is displayed if you monitor the block transfers to the 1770-HT1. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 86 5-38 Supported 1771 Modules Notes: Publication 1757-UM007A-EN-P - April 2002...
  • Page 87: Overview

    2. From a Command Prompt, start NTools with the -u option. 3. If necessary, put NTools in ACTIVE mode. 4. In the NTools network tree, locate and select the 1757-ABRIO module. 5. Right click on the 1757-ABRIO and select Update Firmware from File...
  • Page 88: Controlflash

    -u option so that you can easily update the firmware. ControlFlash Install the ControlFlash software from the 1757-ABRIO distribution CD and run it as you would to update any other module. Refer to the ControlFlash documentation and help for detailed information on how to use ControlFlash.
  • Page 89: Leds

    ControlBus backplane within the last 5 seconds. Yellow Idle, no requests received from the backplane in the last 5 seconds. The module has returned an error to a request from the backplane within the last second. Allen-Bradley HMIs Publication 1757-UM007A-EN-P - April 2002...
  • Page 90: Ok Led - Module Health

    Troubleshooting OK LED - Module Health A bicolor OK LED indicates module health. A red LED indicates that module startup diagnostics have failed or a major module fault such as watchdog bite or jabber inhibit has occurred. Green indicates that the card has passed all power-up diagnostics and is functioning normally.
  • Page 91: Using The Configuration Program For Troubleshooting

    Monitor tags to see if the tag is being updated by the host processor and to see the values of the data that the 1757-ABRIO is sending to or receiving from the host processor. Monitor the diagnostic counters to see if the active station list is correct, to see if the module is sending and receiving packets, and to see if any network errors are occurring.
  • Page 92: Data Is Not Updating

    • Rack is not included in the configuration • Problems with cabling and termination Check the active rack list to see if the 1757-ABRIO shows the rack. View the Scanner Log to see if there are any messages that indicate the source of the problem.
  • Page 93: General Tab

    Connection Tab The Inhibit Module checkbox inhibits the module. Table A.5 If you: Then: • check this box since the 1757-ABRIO have configured the 1757-ABRIO does not use scheduled messaging If this box is checked: Then: • this causes the module to fault the...
  • Page 94: Module Info Tab

    Error Counters • They should all be 0. • The Status at the bottom of the screen indicates the Status status of the connection to the module. • The 1757-ABRIO does not use scheduled messages. Publication 1757-UM007A-EN-P - April 2002...
  • Page 95: Normal Operational Messages

    Operational Comparison Between the 1757-ABRIO and PLC-5 Normal Operational The 1757-ABRIO is designed to respond, as much as possible, like a PLC-5 system. In PLC-5 applications, all I/O modules are physically Messages configured for safe state if the PLC-5 is in Program or Fault mode.
  • Page 96 • Any data “read tag” refers to data being read by a controller. • Any data “write tag” refers to data being written by a controller. Table B.2 Normal Operational Comparison Between the PLC-5 and the 1757-ABRIO 1757-ABRIO ACTIVE or From the PLC-5 Perspective From the 1757-ABRIO Perspective...
  • Page 97 Operational Comparison Between the 1757-ABRIO and PLC-5 Table B.2 Normal Operational Comparison Between the PLC-5 and the 1757-ABRIO 1757-ABRIO INACTIVE and From the PLC-5 Perspective From the 1757-ABRIO Perspective or PLC-5 Program Mode Discrete inputs Discrete input data updates. Data update in the PLC Discrete input data updates in the 1757-ABRIO.
  • Page 98: Exception Handling Messages

    These bits are included when you map a discrete rack or block transfer module to a flag read tag. Exceptions cause messages to be logged in the scanner log. Table B.3 Exception Conditions Comparison Between the PLC-5 and the 1757-ABRIO Exception Condition Message From 1757-ABRIO Perspective From the PLC-5 Perspective •...
  • Page 99 Operational Comparison Between the 1757-ABRIO and PLC-5 Table B.3 Exception Conditions Comparison Between the PLC-5 and the 1757-ABRIO Exception Condition Message From 1757-ABRIO Perspective From the PLC-5 Perspective • Good communication bit for the rack is • Status bit for the rack is cleared...
  • Page 100 Operational Comparison Between the 1757-ABRIO and PLC-5 Table B.3 Exception Conditions Comparison Between the PLC-5 and the 1757-ABRIO Exception Condition Message From 1757-ABRIO Perspective From the PLC-5 Perspective • 1757-ABRIO sets block transfer write data • N/A Numeric write tag times out mapped to the tag to the state set by the user in the module configuration.
  • Page 101 Appendix Specifications The 1757-ABRIO is a standard ControlBus module with the following specifications: Parameter Specification Module Location ProcessLogix or ControlLogix chassis Maximum Backplane Current Load 675 mA @ +5.1V DC and 5 mA @ 24 V DC from I/O chassis backplane...
  • Page 102 Specifications Publication 1757-UM007A-EN-P - April 2002...
  • Page 103 ___Yes, please call me ___Yes, please email me at __________________________ ___Yes, please contact me via ________________________ Return this form to: Allen-Bradley Marketing Communications, 1 Allen-Bradley Dr., Mayfield Hts., OH 44124-9705 Allen-Bradley HMIs Phone: 440-646-3176 Fax: 440-646-3525 Email: RADocumentComments@ra.rockwell.com Publication ICCG-5.21- January 2001...
  • Page 104 PLEASE FASTEN HERE (DO NOT STAPLE) Other Comments PLEASE FOLD HERE NO POSTAGE NECESSARY IF MAILED IN THE UNITED STATES BUSINESS REPLY MAIL FIRST-CLASS MAIL PERMIT NO. 18235 CLEVELAND OH POSTAGE WILL BE PAID BY THE ADDRESSEE 1 ALLEN-BRADLEY DR MAYFIELD HEIGHTS OH 44124-9705...
  • Page 105 Allen-Bradley HMIs...
  • Page 106 Publication 1757-UM007A-EN-P - April 2002 PN 957657-44 Copyright © 2002 Rockwell Automation. All rights reserved. Printed in the U.S.A.
  • Page 107 Allen-Bradley HMIs...

Table of Contents