Mount The Repeater Module - Allen-Bradley ControlNet 1786-RPCD Installation Instructions Manual

Dual copper repeater module
Hide thumbs Also See for ControlNet 1786-RPCD:
Table of Contents

Advertisement

Mount the Repeater Module

To mount the module on the DIN rail:
ATTENTION
1. Position the module on the 35×7.5mm DIN rail (Allen-Bradley part number
199-DRI; 46277-3; EN 50022) at a 30° angle.
IMPORTANT
2. Hook the module lip (on the rear of the module) onto the top of the DIN rail and
rotate the module onto the rail.
3. Press the module down to the DIN rail until the module is flush with the rail.
The locking tab should snap into position and lock the module onto the DIN rail. If
the tab does not snap into position, follow step 4. If the tab does snap into position,
go to step 5.
This product is grounded through the DIN rail to chassis ground.
Use zinc plated yellow-chromate steel DIN rail to assure proper
grounding. The use of other DIN rail materials (e.g., aluminum,
plastic, etc.) that can corrode, oxidize, or are poor conductors, can
result in improper or intermittent grounding.
To ensure proper operation of the 1786-RPCD repeater module, you
must position the 1786-RPCD module to the left of any 1786-RPFRL or
1786-RPFRXL repeater modules in your configuration.
ControlNet Dual Copper Repeater Module
Publication 1786-IN001B-EN-P - May 2004
9