Installation Instructions
ControlNet Modular Repeater
Medium-distance Fiber Module
Catalog Number 1786-RPFM
Topic
About the Module
Use the 1786-RPFM module when you need a medium-distance fiber link
between two ControlNet products. Maximum distance is 3000 m (9843 ft). The
fiber link provides ground isolation between nodes and is less susceptible to
noisy environments than copper media.
The supported distance depends on the quality of the fiber,
IMPORTANT
number of splices, and connectors. The total light loss through
the fiber link must be less than 13.3 dB.
AB Driv
Page
2
3
4
5
6
6
10
11
12
13
17

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ControlNet 1786-RPFM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Allen-Bradley ControlNet 1786-RPFM

  • Page 1: Table Of Contents

    Installation Instructions ControlNet Modular Repeater Medium-distance Fiber Module Catalog Number 1786-RPFM Topic Page Important User Information Environment and Enclosure North American Hazardous Location Approval European Hazardous Location Approval Module Components Mount the Module Select Fiber Cable Connect the Fiber Module Troubleshoot the Module Specifications Additional Resources...
  • Page 2: Important User Information

    2 ControlNet Modular Repeater Medium-distance Fiber Module Important User Information Solid-state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature/) describes some important differences between solid-state equipment and hard-wired electromechanical devices.
  • Page 3: Environment And Enclosure

    ControlNet Modular Repeater Medium-distance Fiber Module 3 Environment and Enclosure ATTENTION: This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC 60664-1), at altitudes up to 2000 m (6562 ft) without derating.
  • Page 4: North American Hazardous Location Approval

    4 ControlNet Modular Repeater Medium-distance Fiber Module North American Hazardous Location Approval The following information applies Informations sur l’utilisation de cet when operating this equipment in équipement en environnements hazardous locations. dangereux. Products marked "CL I, DIV 2, GP A, B, C, D" are Les produits marqués "CL I, DIV 2, GP A, B, C, D"...
  • Page 5: European Hazardous Location Approval

    ControlNet Modular Repeater Medium-distance Fiber Module 5 European Hazardous Location Approval European Zone 2 Certification (The following applies when the product bears the Ex Marking.) This equipment is intended for use in potentially explosive atmospheres as defined by European Union Directive 94/9/EC and has been found to comply with the Essential Health and Safety Requirements relating to the design and construction of Category 3 equipment intended for use in potentially explosive atmospheres, given in Annex II to this Directive.
  • Page 6: Module Components

    Both sides of the module contain a backplane connector. 42505 Mount the Module Mount the module on a 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail, Allen-Bradley part number 199-DR1, 46277, EN 50022. ATTENTION: This product is grounded through the DIN rail to chassis ground.
  • Page 7 ControlNet Modular Repeater Medium-distance Fiber Module 7 Mounting Dimensions (4.44) (2.76) (4.0) 101.2 (4.048) (3.6) 42501 All dimensions are in mm (in.). 1. Position the module at a 30 ° angle. 42507 2. Hook the lip on the back of the module to the top of the DIN rail and press the bottom of the module until the locking tab snaps securely in place.
  • Page 8 8 ControlNet Modular Repeater Medium-distance Fiber Module WARNING: If you insert or remove the module while backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
  • Page 9 ControlNet Modular Repeater Medium-distance Fiber Module 9 Then You will use a channel Remove the protective cap from the channel. You will not use a channel Keep the protective cap on to protect the channel from dust. You place the module in storage Keep the protective cap on to protect the channel from dust.
  • Page 10: Select Fiber Cable

    10 ControlNet Modular Repeater Medium-distance Fiber Module You can attach a maximum of four modules to the repeater adapter, or, the number of modules whose total power consumption does not exceed 1.6 A @ 5V DC, whichever occurs first. If you exceed the module or power limit, you may damage the IMPORTANT repeater adapter and modules.
  • Page 11: Connect The Fiber Module

    ControlNet Modular Repeater Medium-distance Fiber Module 11 Connect the Fiber Module If you are wiring only one channel, you can use either channel 1 or channel 2. Do these steps to connect to channel 1, receive (RX). 1. Align the knob of the cable connector with the groove of the module connector.
  • Page 12: Troubleshoot The Module

    12 ControlNet Modular Repeater Medium-distance Fiber Module Troubleshoot the Module Use the channel 1 or 2 status indicators to check module status and troubleshoot the module. Channel 1 Status Channel 2 Status 30041 Indicator Probable Cause Repeater not connected to the power supply. Green Channel is operating normally.
  • Page 13: Specifications

    ControlNet Modular Repeater Medium-distance Fiber Module 13 Specifications Technical Specifications - 1786-RPFM Attribute Value All supply voltages or voltage ranges Backplane: 5V DC, 400 mA Dissipation Communication rate 5 Mbps Mounting orientation Any mounting orientation Minimum enclosure size (HxWxD), approx 304.8 x 196.8 x 101.6 mm (12 x 7.75 x 4 in.) Fiber type...
  • Page 14 14 ControlNet Modular Repeater Medium-distance Fiber Module Environmental Specifications - 1786-RPFM Attribute Value Temperature, operating 0…60 °C (32…140 °F) IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock) Temperature, surrounding air, max 60 °C (140 °F) Temperature, nonoperating -40…85 °C (-40…185 °F)
  • Page 15 ControlNet Modular Repeater Medium-distance Fiber Module 15 Environmental Specifications - 1786-RPFM Attribute Value Emissions Group 1, Class A CISPR 11 ESD immunity 4 kV contact discharges 8 kV air discharges IEC 61000-4-2 Radiated RF immunity 10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz 10V/m with 200 Hz 50% Pulse 100% AM at IEC 61000-4-3...
  • Page 16 16 ControlNet Modular Repeater Medium-distance Fiber Module Certifications - 1786-RPFM Certification Value UL Listed Industrial Control Equipment. See UL File E65584. CSA Certified Process Control Equipment. See CSA File LR54689C. CSA Certified Process Control Equipment for Class I, Division 2 Group A, B, C, D Hazardous Locations.
  • Page 17: Additional Resources

    ControlNet Modular Repeater Medium-distance Fiber Module 17 Additional Resources These documents contain additional information concerning related Rockwell Automation products. Resource Description ControlNet Coax Taps Installation Document contains procedures and Instructions, publication 1786-IN007 specifications for the installation of ControlNet coaxial taps. ControlNet Coax Media Planning and Document describes the components and Installation Guide, publication...
  • Page 18 18 ControlNet Modular Repeater Medium-distance Fiber Module Notes: Rockwell Automation Publication 1786-IN011C-EN-P - November 2010...
  • Page 19 ControlNet Modular Repeater Medium-distance Fiber Module 19 Notes: AB Driv Rockwell Automation Publication 1786-IN011C-EN-P - November 2010...
  • Page 20 RA-DU002, available at http://www.rockwellautomation.com/literature/. Allen-Bradley, Rockwell Software, Rockwell Automation, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies. Rockwell Otomasyon Ticaret A.Ş., Kar Plaza İş Merkezi E Blok Kat:6 34752 İçerenköy, İstanbul, Tel: +90 (216) 5698400...

Table of Contents