6 ControlNet Modular Repeater Medium-distance Fiber Module

Module Components

The illustration shows the components that comprise the 1786-RPFM module.
Indicators
Protective Caps
Channel 1
Fiber Port
Module Locking Tab
Both sides of the module contain a backplane connector.

Mount the Module

Mount the module on a 35 x 7.5 mm (1.38 x 0.30 in.) DIN rail, Allen-Bradley
part number 199-DR1, 46277, EN 50022.
ATTENTION: This product is grounded through the DIN rail to
chassis ground. Use zinc-plated yellow-chromate steel DIN rail to
assure proper grounding. The use of other DIN-rail materials (for
example, aluminum or plastic) that can corrode or oxidize, or are
poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every
200 mm (7.87 in.) and use end-anchors appropriately.
TIP
Rockwell Automation Publication 1786-IN011C-EN-P - November 2010
When using the 1786-RPFM module, we recommend horizontal
mounting if cabinet temperatures are expected to approach
60 °C (140 °F). If your expected temperatures are much lower
than 60 °C (140 °F), vertical mounting is acceptable. If using
vertical mounting, we recommend that the 1786-RPA repeater
adapter module be mounted at the top.
Channel 2 Fiber Port
Right-side
Backplane
Connector
with
Protective
Cover
42505