Ac Power Monitoring Enable / Disable - Phonetics Sensaphone 4100 User Manual

Version 5.41
Table of Contents

Advertisement

Sensaphone Model 4100 Instruction Manual
The 4100 will say "Off " to indicate that the high temperature alarm is disabled, or
"On" to indicate that it is enabled.
3. Repeat key sequence to change
To enable/disable the low temperature alarm:
1. Press the SENSOR ON/OFF key
2. Press the LOW TEMP key
The 4100 will say "Off " to indicate that the high temperature alarm is disabled, or
"On" to indicate that it is enabled.
3. Repeat key sequence to change
To interrogate:
1. Press the WHAT IS key
2. Press the HIGH TEMP key to check the high temperature alarm. Press the LOW
TEMP key to check the low temperature alarm.
If the high or low temperature alarm is enabled, the 4100 will recite the programmed limit
in degrees (see Temperature Limits above). If the high or low temperature alarm is disabled,
the 4100 will say "Off " and then recite the programmed limit in degrees.

AC POWER MONITORING ENABLE / DISABLE

The Model 4100 monitors AC power failure. This command enables or disables the power
failure detection feature. When enabled, the Model 4100 will monitor power and dial out if
a valid failure occurs (see AC POWER RECOGNITION TIME below). When disabled, the
Model 4100 will not dial out for a power failure alarm. The default setting is enabled (on).
To enable/disable the AC power failure alarm:
1. Press the SENSOR ON/OFF key
2. Press the ELECT key
The 4100 will say "Off " to indicate that the power alarm is disabled, or the 4100 will
say "On" to indicate that the power alarm is enabled.
32
(or)