This chapter explains the monitoring capabilities and keyboard commands to program the
monitoring functions of the Model 4100. This includes:

Enable/disable inputs

Input recognition time
Configure input normality (The ID Number)
Enable/disable temperature input
Temperature limits
AC power monitoring enable/disable
AC power recognition time
High sound monitoring
Disable high sound alarm
De-sensitize sound monitoring
ENABLE/DISABLE INPUTS
This function allows you to enable or disable an input (1-3, AUX TEMP) from dialing out
during an alarm. An enabled input will respond to an alarm and allow dialout. A disabled
input will not initiate a dialout. This command is useful while you are wiring your inputs
(see pages 9-10), or at any other time you would like the alarms to be ignored. The default
setting for all inputs is enabled (on).
To enable/disable inputs:
1. Press the SENSOR ON/OFF key
2. Press the number of the input to enable/disable (1, 2, 3, or 4 for AUX TEMP)
The unit will say "Off " to indicate disabled or "On" to indicate enabled.
3. Repeat key sequence to change
To interrogate:
1. Press the WHAT IS key
2. Press the number of the input (1-4)
If the input is enabled, the 4100 will recite the Phone number programmed for that
digit. If it is disabled, the unit will say "Off " and then recite the Phone number.