Step 3: Ignite The Burner (Rm0050-Rm0700 Only) - Eclipse RatioMatic RM Series Installation Manual

Table of Contents

Advertisement

BV shaft shown in
closed position
Figure 4.5. Air Butterfly Valve Shaft
NOTE: Steps 3-5 RM0050-RM0700 Only (see page 20 for
RM1000-RM3000)
Low fire start without high turndown option Procedure "A".
Main gas
shut-off
valve train
NOTE: The ratio regulator is factory set. Use Procedure "A"
only if burner does not ignite or requires further adjustment.
Bypass start gas without fuel orifice meter Procedure "C".
Main gas
shut-off
valve train
NC
NC
14
Step 3: Ignite the Burner (RM0050-RM0700
only)
■ This procedure is written with the assumption the
burner has a flame monitoring control system
installed and operating. A proper purge cycle must
be part of the system and purge timing should not
be bypassed.
Determine system layout and use the applicable ignition
procedure.
Low fire start with high turndown option Procedure "B".
Ratio regulator
adjusting screw
Main gas
shut-off
valve train
NOTE: The RatioMatic burner with high turn down option
includes a ratio regulator with internal bypass adjustment.
Bypass start gas with fuel orifice meter Procedure "D".
Main gas
shut-off
valve train
Figure 4.6.
Eclipse RatioMatic Burners, RM Series, V5, Installation Guide 110, 12/3/2014
WARNING
with bypass
NC
NC