17.6 G(P).PRR

Setting data
Internal device
Bit
(S)
(D)
[Instruction code]
G.PRR
GP.PRR
Setting data
Setting data
Start I/O signal of the module
Un
(00 to FE: The 2 upper digits of an input/output signal expressed in 3-digit.)
(S)
Head number of the devices that store control data
Head bit device number of the local station that turns ON for one scan upon instruction
completion.
(D)
(D)+1 also turns on if the execution completes abnormally.
Control data
Device
Item
(S)+0
Transmission channel
(S)+1
Transmission result
CR/LF addition
(S)+2
designation
(S)+3
Transmission pointer
(S)+4
Output count
17 - 24
In non procedure protocol communication, this instruction transmits data using a user
frame according to the data specified in the transmission user frame designation area.
Link direct device
File
register
Word
Bit
[Executing
condition]
Command
Command
Description
The file registers of each of the local device and the program cannot be used as setting data.
Designate the transmission channel.
1: Channel 1 (CH1 side)
2: Channel 2 (CH2 side)
The transmission completion result by the PRR instruction is stored.
0
: Normal
Other than 0: Error code
Designate whether or not to add CR/LF to the transmission data.
0: Do not add CR/LF.
1: Add CR/LF.
Transmission user frame designation area designates from which
the frame number data may be transmitted.
Designate the number of user frames to be transmitted.
REMARKS
(1) For information about errors caused by incorrect data designated by the user,
see the description in "Errors" on the next page.
(2) The "Set by" column indicates the following:
• User
: Data set by the user before executing the dedicated instruction.
• System: The programmable controller CPU stores execution results of the
dedicated instruction.
Applicable device
Intelligent function
J \
module device
U \G
Word
G.PRR
GP.PRR
Setting data
17 DEDICATED INSTRUCTIONS
Index
register
Constant
Zn
Un
(S)
(D)
Un
(S)
(D)
Set by
User
User, System Device name
System
Setting range
1, 2
0, 1
1 to 100
1 to 100
Others
Data type
BIN-16 bit
Bit
Set by
User
System
User
User
User
17- 24