Installation & User Guide
1. General
Ambient operating temperature
Ambient storage temperature
Temperature media
Mechanical environment
Electromagnetic environment
Pressure
MID
1.1 Inside the box
Description of components included in the box
1 x
Energy meter
Note: For cooling meters a wall mounting kit is delivered with the product
2. Installation
2.1 Preparation
SonoSelect incorporates a tamper monitoring function. If the
calculator is opened the meter will set alarm E13 in display.
Don't open unless for adding communication module,
replacing battery or installing cables.
Reset requires Bluetooth dongle 014U1963 and SonoApp
service tool.
SonoSelect is delivered with the option of reconfiguring
supply/return using the Bluetooth dongle 014U1963 and
SonoApp service tool.
Note:
• Product is approved for ambient temperature between 5-55 °C, non-condensing (indoor installation). It is recommended
to install Calculator at max. 45 °C to secure optimal conditions for battery lifetime. At media temperatures below ambient
temperature (cooling) the calculator must be mounted separately from the flow sensor to prevent condensation.
• Avoid installation stress from pipes and fittings.
• Flush the system.
4 | © Danfoss | Energy Meters | 2018.01
SonoSelect and SonoSafe
2 x Gaskets &
1 temperature
sensor O-ring
class A 5 - 55 °C (Indoor installation, non-condensing)
-25 - 60 °C
5 - 95 °C
class M2
class E1
PN16
Accuracy Class 2
4 x
Wired seals
1 x
Installation
& User Guide
VUIGB802
Need help?
Do you have a question about the SonoSafe and is the answer not in the manual?