Leakwise ID-220 SERIES User Manual page 81

Smart leakwise controller & smart leakwise receiver for remote slc-220’s
Table of Contents

Advertisement

81
3.
Ferrites on ID-223 / ID-227 sensor cable at SLC-220
This is in addition to a ferrite installation close to the sensor – Refer to Sensor User Guide.
Ferrite type 1: Laird 28A5131-0A2, Qty: 1
Number of turns (as seen inside the ferrite core): 4
Ferrite type 2: Laird 28A2024-0A0, Qty: 1
Number of turns (as seen inside the ferrite core): 2
The pictures depict installation for SLC-220/Basic. For SLC-220/Multi it may not be possible to
install all ferrites inside the enclosure.
EMC Filter board should be installed on every occupied sensor input.
SLC-220 User Guide Rev 2.0
June 2018

Hide quick links: