5 Using the optional front panel LCD

The 4.3" graphic color display with integrated touch panel enables the viewing of sensors status
and parameters, and enables setting of the parameters in a similar way as with the SLC-Manager
PC program.
The SLC-220 button is the entry to screens that show parameters which influence general
features that influence all the sensors.
Sensor #1 through Sensor #4 buttons are used to view and set Individual sensors.
The System Overview Screen shows the sensors status and names & a corresponding Bar-
graph for each active sensor.
Bar-graph interpretation:
Sensor status
Water
Signal too low
Signal too high
Air
Oil and High Oil
The small blue button named "i" is not relevant for any settings. Pressing it shows company logo,
power supply voltage, Main board serial number and its' Software version.
The empty area on the left side of "i" is reserved for optional error messages.
Both SLC-220 and Sensors settings have two levels of parameters: Normal and Advanced. As
implied by the name, the "Normal" parameters are those which may be required to change during
SLC-220 User Guide Rev 2.0
System Overview Screen
Bar-graph fill percentage
20%
20%
20%
Full (100%)
1%(min. oil) ÷ 100% (max. oil)
Bar-graph color
Green
Yellow
Yellow
Yellow
Red
June 2018