Pressing the Advanced button enables an Administrator user to view and change additional
special parameters:
Pressing the View Parameters button returns the display to the basic SLC-220 parameters.
1.
Administrator Password: Initial password is 5678.
2.
Project Index: All SLC-220 units considered as a single group in a site will have the same
project index. The index can be between 1 and 65536. This is important when working
under a common controller, such as SLR-220.
3.
Hysteresis: A value in µA that is added / subtracted to/from the calculation of each cross-
point between two adjacent statuses. This can be 1, 3 5 or 10 µA. A lower number is good
for operation in calm water, a higher number is better for turbulent water.
4.
Test Mode: For firmware version 4.1 or later. For normal and default SLC-220 operation,
the setting is No. After selecting Yes, the scanning of the enabled sensors is slowed down
significantly, to enable current measurement of sensors wires with a mA meter. A beep
from the Main board is heard every 10 seconds, when the next sensor is powered. Status
updates are slowed down, therefore it is the responsibility of the user to exit the Test Mode
at the end of the test.