Leakwise ID-220 SERIES User Manual page 18

Smart leakwise controller & smart leakwise receiver for remote slc-220’s
Table of Contents

Advertisement

If the SLC-220 unit is equipped with Outputs board/s, pass the 4-20mA cable through the proper
cable gland in the external wall of the enclosure. Then connect the two wires to the contacts of
terminal block TB19 as follows:
TB19 Contact
If 0-5 V output is required (instead of 4-20 mA), connect each of the two wires to TB19 as follows:
TB19 Contact
Note: At this point, the current / voltage output is not galvanically isolated.
Setting the functionality / range of the output is done by jumpers on the Outputs board:
JP5 position
2-3
1-2
2-3
1-2
SLC-220 User Guide Rev 2.0
Iout
GND
Vout
GND
JP6 position
2-3
2-3
1-2
1-2
Contact Function
4-20 mA + (Current source, non-isolated)
4-20 mA - (Current return, non-isolated)
Contact Function
0-5 V + (non-isolated)
0-5 V return (non-isolated)
Range at TB19
0-5 V
4-20 mA < This is the default setting
0-20 mA
0-24 mA
18
June 2018

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Slr-220Slc-220

Table of Contents