For SLC-220/Basic, the lower board is associated with sensor #1; the upper board (if installed) is
associated with sensor #2.
Pass the cable through the proper cable gland in the external wall of the enclosure. Then connect
the wires of this cable to the contacts of terminal blocks TB14 till TB18 of the appropriate Outputs
board as follows:
Relay number
#1
#2
#3
#4
#5
NO:
Normally Opened contact,
COM: Common point,
NC:
Normally Closed contact.
Arranging the wires:
In SLC-220/Multi, there is one white plastic wire saddle above every Outputs board. Insert the
wires into the saddles and guide them to the left of the enclosure, then down and to the cable
gland.
Each relay has an indicating LED on the board to indicate when it is energized.
The relays can be set to operate in normal mode or in fail-safe mode. Changing the setting is
done in SLC-220 Settings (chapter 4.5).
SLC-220 User Guide Rev 2.0
Indicated Status
Water or
Oil / High Oil for sensor #1
Oil or
Oil / High Oil for sensor #2
High Oil or
Oil / High Oil for sensor #3
Air or
Oil / High Oil for sensor #4
Fail or
Common Fail for all sensors
Terminal Block
TB14
TB15
TB16
TB17
TB18
20
Contacts
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
June 2018