Notes regarding room temperature hook-up (RS function) for remote control units

Never activate the RS function for underfloor heating circuits (iner-
tia).
Information on the Vitotrol 200-A and Vitotrol 300-A
For every heating circuit in a heating system, a Vitotrol 200-A or
Vitotrol 300-A can be used.
The Vitotrol 200-A can regulate one heating circuit; the
Vitotrol 300-A up to three heating circuits.
5
Up to two remote controls can be connected to the control unit.
Vitotrol 200-A
Part no. Z008341
KM BUS subscriber
■ Displays:
– Room temperature
– Outside temperature
– Operating condition
■ Settings:
– Set room temperature for standard mode (normal room tempera-
ture)
Note
The set room temperature for reduced mode (reduced room
temperature) is set at the control unit.
– Operating program
■ Party and economy mode can be enabled via keys
■ Integral room temperature sensor for room temperature hook-up
(only for one heating circuit with mixer)
VIESMANN
86
1 3
0
3 V–
868 MHz
< 10 mW
approx. 25 to 30 m inside buildings,
subject to construction
IP 20 to EN 60529
Ensure through design/installation
Function type
RS type 1B to EN 60730-1
Permissible ambient temperature
– Operation
0 to +40 °C
– Storage and transport
–25 to +65 °C
Setting range
– Comfort temperature
10 to 40 °C
– Setback temperature
10 to 40 °C
– Frost protection temper-
ature
5 °C
Power reserve during bat-
tery change
3 min
Specification, receiver
Operating voltage
230 V~± 10 % 50 Hz
Rated breaking capacity of the floating contact
– max.
6(1) A, 230 V~
– min.
1 mA, 5 V–
IP rating
IP 20 to EN 60529
Ensure through design/installation
Safety category
II to EN 60730-1 subject to correct in-
stallation
Permissible ambient temperature
– Operation
0 to +40 °C
– Storage and transport
–25 to +65 °C
In heating systems with a heating circuit without mixer and heating
circuits with mixer, the RS function must only affect the heating cir-
cuit with mixer.
Note
Hardwired remote control units cannot be combined with the wire-
less base station.
Installation location:
■ Weather-compensated mode:
installation anywhere in the building
■ Room temperature hook-up:
the integral room temperature sensor captures the actual room
temperature and effects any necessary correction of the flow tem-
perature.
The captured room temperature depends on the installation site:
– Main living room on an internal wall opposite radiators
– Not on shelves or in recesses
– Never in the immediate vicinity of doors or close to heat sources
(e.g. direct insolation, fireplace, TV set, etc.).
Connection:
■ 2-core lead, length max. 50 m (even if connecting several remote
control units)
■ Never route this cable immediately next to 230/400 V cables.
■ LV plug as standard delivery