Notes Regarding Room Temperature Hook-Up (Rs Function) For Remote Control Units; Information On The Vitotrol 200A And Vitotrol 300A; Vitotrol 200A - Viessmann VITODENS 200-W Technical Manual

Gas condensing boilers 17.0 to 150.0 kw as multi boiler system up to 900.0 kw
Table of Contents

Advertisement

Control units
(cont.)
Setting range
– Comfort temperature
– Setback temperature
– Frost protection temperature
Power reserve during battery
change
Specification, receiver
Operating voltage
Rated breaking capacity of the float-
ing contact
– max.
– min.

Notes regarding room temperature hook-up (RS function) for remote control units

Never activate the RS function for underfloor heating circuits (iner-
tia).

Information on the Vitotrol 200A and Vitotrol 300A

One Vitotrol 200A or one Vitotrol 300A can be used for every heating
circuit in a heating system.
The Vitotrol 200A can regulate one heating circuit; the Vitotrol 300A
up to three heating circuits.
Up to two remote controls may be connected to the control unit.

Vitotrol 200A

Part no. Z008 341
KM BUS subscriber
■ Indications:
– Room temperature
– Outside temperature
– Operating condition
■ Settings:
5
– Set room temperature for standard mode (day temperature)
Note
The set room temperature for reduced mode (night temperature)
is set at the control unit.
– Operating program
■ Party and economy mode can be enabled via keys
■ Integral room temperature sensor for room temperature hook-up
(only for one heating circuit with mixer)
Installation site:
■ Weather-compensated mode:
Installation anywhere in the building.
■ Room temperature hook-up:
The integral room temperature sensor captures the actual room
temperature and corrects the flow temperature if necessary.
The captured room temperature is dependent on the installation site:
– Main living room on an internal wall opposite radiators.
– Not on shelves or in recesses.
– Never install immediately by a door or heat source (e.g. direct
sunlight, fireplace, TV set, etc.).
Connection:
■ Two-core cable, length max. 50 m (even if connecting several
remote control units).
■ Never route this cable immediately next to 230/400 V cables.
■ LV plug as standard delivery.
VIESMANN
56
10 to 40 °C
10 to 40 °C
5 °C
3 min
230 V~ ± 10 % 50 Hz
6(1) A, 230 V~
1 mA, 5 V–
IP rating
Safety category
Permissible ambient temperature
– during operation
– during storage and transport
In heating systems with a heating circuit without mixer and heating
circuits with mixer, the RS function must only affect the heating circuit
with mixer.
Note
Hardwired remote control units cannot be combined with the wireless
base station.
1 4
8
Specification
Power supply via KM BUS
Power consumption
Safety category
IP rating
Permissible ambient temperature
– during operation
– during storage and transportation
Setting range of the set room tempera-
ture for standard mode
IP 20 to EN 60529
ensure through appropriate
design/installation
II to EN 60730-1 subject to cor-
rect installation
0 to +40 °C
–25 to +65 °C
0.2 W
III
IP 30 to EN 60529
Ensure through design/in-
stallation
0 to +40 °C
−20 to +65 °C
3 to 37 °C
VITODENS 200-W