Simplex TrueAlarm 4100 Series Manual
Simplex TrueAlarm 4100 Series Manual

Simplex TrueAlarm 4100 Series Manual

Fire alarm control and indicating equipment

Advertisement

Quick Links

EN54 Compliant*
Features
Conforms to EN54-2 and EN54-4 Standards*
Control panel hardware feature summary:
• 160 Character super-twist LCD readout
(4 lines x 40 characters/line)
• Membrane keypad with insert labels
• Expandable up to 512 points/32 zones
Supports conventional and addressable
inputs:
• MAPNET II
®
Addressable Devices including
isolator modules
• TrueAlarm
®
Addressable Analog Sensors**
• Nonvolatile flash EPROM memory
• Temperature compensated battery charger
• Battery supervision (low/no battery)
Software Features:
• Four operator access levels
• 300 Event historical alarm and fault logs
• Zonal and point alarm information
• Alarm resound feature
Programmable:
• Site specific programmable keys/LEDs
• Powerful custom control provides maximum
flexibility
Optional Voice Evacuation and Fire Brigade
phones:
• Single, dual, and triple channel
• Custom voice messages and tones
• 2-Way fire brigade voice communications
• 25 W and 100 W, 25 VRMS Amplifiers
Interface to Remote:
• MINIPLEX
®
Transponders
• 4604-9202UK Remote LCD Annunciator for
supplementary operations
Optional Modules:
• 4120 Network Interface
• Sounder outputs
• Conventional and addressable inputs
• Control relays with feedback
• Mimic panel modules
• Expansion power supplies
© 1999 Simplex Time Recorder Co. All rights reserved.
®
TrueAlarm
Fire Alarm Controls
4100 and 4120 Series Fire Alarm
Control and Indicating Equipment (c.i.e)
*** System is Normal ***
09:36:24
MON 05-APR-1999
FIRE
SOUNDER
SOUNDERS
ALARM
FAULT
DISABLEMENT
FAULT/DISABLED
SILENCED
REVIEW
REVIEW
REVIEW
DISABLE/ENABLE
SOUNDER
ALARMS
FAULTS
DISABLED
SOUNDERS
SILENCE/RESOUND
ZONES
SYSTEM
FAULT
SITE SPECIFIC PROGRAMMABLE KEYS/LEDS
4100
FIRE ALARM CONTROL
4100/4120 Series Control and Indicating Equipment
(shown as a 6 unit panel with optional voice control)
Description
Simplex 4100/4120 Series Control and Indicating
Equipment provide an extensive and powerful feature
list to satisfy a wide variety of applications and local
requirements. They are on-site programmable to
provide mapping logic for inputs and outputs and for
custom labeling additions and revisions. Their flexible
site-specific software features can be quickly and
securely generated, modified, and archived by trained
service personnel using computer based programming
tools. With this flexibility, last minute changes can be
made on-site, minimizing delays in job completion.
Input point expansion is available up to a maximum of
512 points in any combination of input types.
NOTE: When these c.i.e. products are factory configured for 4120
Network Control panel operation, substitute 4100 for 4120.
Contact your local Simplex representative for additional
information about the 4120 Network.
* Refer to pages 6 and 7 for additional information on EN54 compatibility and
LPC testing status.
** MAPNET II addressable communications is protected under U.S. Patent #
4,796,025. TrueAlarm addressable smoke detection operation is protected
by one or more of the following U.S. Patents: 5,155,468; 5,173,683;
5,543,777; 5,400,014; 5,552,765; 5,552,763; DES. 377,460.
PULL DOOR TO OPEN
EMERGENCY OPERATING
INSTRUCTIONS
INDICATION OF ALARM, FAULT WARNING, OR DISABLED CONDITION:
- GENERAL VISIBLE INDICATOR AND AUDIBLE INDICATOR ON.
TO VIEW SUPPRESSED ALARM, FAULT, OR DISABLED INDICATIONS:
- PRESS "REVIEW" KEY LOCATED UNDER EACH VISIBLE INDICATOR.
- REPEAT UNTIL ALL SUPPRESSED INDICATIONS HAVE BEEN DISPLAYED.
RESET
TO SILENCE THE LOCAL AUDIBLE INDICATIONS:
- PRESS "PANEL SILENCE" KEY.
PANEL
SILENCE
TO SILENCE THE ALARM SIGNALS:
- PRESS "SOUNDER" SILENCE/RESOUND" KEY.
TO RESTORE SYSTEM TO NORMAL:
POWER
-PRESS "RESET" KEY.
S4100-0025 (EN54) 5/99

Advertisement

Table of Contents
loading

Summary of Contents for Simplex TrueAlarm 4100 Series

  • Page 1 4,796,025. TrueAlarm addressable smoke detection operation is protected by one or more of the following U.S. Patents: 5,155,468; 5,173,683; • Mimic panel modules 5,543,777; 5,400,014; 5,552,765; 5,552,763; DES. 377,460. • Expansion power supplies S4100-0025 (EN54) 5/99 © 1999 Simplex Time Recorder Co. All rights reserved.
  • Page 2: Operator Interaction

    LEDs provide custom operations on a sounder circuit and turns on steady when a sounder circuit labeling (labels insert into a is disabled, DISABLE/ENABLE SOUNDERS KEY allows all pocket) sounders to be disabled simultaneously Simplex Time Recorder Co. S4100-0025 (EN54) 5/99...
  • Page 3 – Modules contain socketed LEDs to allow as Class B operation interchanging with different color LEDs to indicate – Capable of supporting two-wire Simplex smoke function detectors and electronic heat detectors plus normally – Switch modules can be used to perform manual...
  • Page 4 • Frequency response of 120 to 12,000 Hz • Secondary Voice/Tone Generator (Optional) • Battery backup capability • Phone to Audio Interface • Integral amplifier monitor for supervised operation • Optional redundant operation automatically switches-over from primary to backup amplifier Simplex Time Recorder Co. S4100-0025 (EN54) 5/99...
  • Page 5: Operation

    Master Controller to direct the request • Telephone circuits are supervised for open and short routing of the audio tones, codes, prerecorded or manual voice messages to the appropriate audio output circuit conditions circuits. Simplex Time Recorder Co. S4100-0025 (EN54) 5/99...
  • Page 6: Product Selection

    “Retainer” = only occupies space at retainer panel level and internal modules can be located behind. Module Size Reference: Each unit of space has 16” (406 mm) of panel width available. (8” = 203 mm, 4” = 102 mm, 2” = 51 mm) Simplex Time Recorder Co. S4100-0025 (EN54) 5/99...
  • Page 7 4” Retainer 0441 Remote Phone N.A. (2) LPC Approval pending. (3) Tested by LPC to verify that no detrimental effect occurred to mandatory EN54 functions. * Refer to Simplex document S4100-0005 for additional information. Simplex Time Recorder Co. S4100-0025 (EN54) 5/99...
  • Page 8: Mounting Information

    Solar Radiation 700 W/cm Simplex, the Simplex logo, MAPNET, and TrueAlarm are either trademarks or registered trademarks of Simplex Time Recorder Co. in the U.S. and/or other countries. S4100-0025 (EN54) 5/99 Gardner, Massachusetts 01441-0001 USA visit us on the world wide web at www.simplexnet.com...

This manual is also suitable for:

Truealarm 4120 series

Table of Contents