Dependent Airflow Control - Price FFU series Installation And Service Manual

Fan filter unit
Hide thumbs Also See for FFU series:
Table of Contents

Advertisement

FAN FILTER UNIT
INSTALLATION & SERVICE INSTRUCTIONS
Ducted Supply – Pressure Independent and Dependent Airflow Control
NOTE:
If a ducted return or return mixing box is used, a PSC, ECM Constant Torque or ECM Constant Flow (preferred) can be used.
STEP 1: If return mixing box is used, turn primary air off. If ducted return, proceed directly to Step 2.
STEP 2: Set FFU to desired flow using appropriate speed controller flow equations (Page 34).
STEP 3: Confirm airflow using flow hood and adjust speed controller as required.
STEP 4: Power up the primary airflow control device. (Ductwork should have been previously balanced).
STEP 5: Measure airflow using flow hood and compare against scheduled flow. Adjust speed controller as necessary to achieve
design airflow.
FIGURE 45: FFU WITH DUCTED RETURN.
FIGURE 46: FFU WITH RETURN MIXING BOX.
priceindustries.com | FAN FILTER UNIT - Manual
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ffu-he-rsr-fc

Table of Contents