STEP 3: Make note of all wire locations for re-installation later. It is recommended to take a picture of all applicable wires.
STEP 4: Open control box and disconnect wires at the terminal block, referencing applicable wiring diagram.
STEP 5: Remove the 6 bolts to free the motor/blower assembly, using a 7/16" socket wrench (or equivalent).
FIGURE 26: MOTOR - BLOWER ASSEMBLY.
STEP 6: Remove motor/blower assembly.
STEP 7: Inspect and/or replace parts.
STEP 8: Replace with the new motor/blower assembly and reassemble by reversing the above steps.
NOTE:
For information on how to order replacement motor/blowers, contact your local Price Sales Representative. Visit Price's
website (http://www.priceindustries.com/contact/reps-dealers) to locate your local Representative.
STEP 9: Double check airflow to ensure that set point has not changed.
27