Optional Accessories; Aerosol Sample Port, Static Port And; Aerosol Injection Port (Inj) - Price FFU series Installation And Service Manual

Fan filter unit
Hide thumbs Also See for FFU series:
Table of Contents

Advertisement

FAN FILTER UNIT
INSTALLATION & SERVICE INSTRUCTIONS

Optional Accessories

Aerosol Sample Port, Static Port and Aerosol Injection Port (INJ)
Sample line string below:
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
STEP 1: If unit has room side removable filter (RSR), remove diffusers perforated face by turning quarter turn fasteners holding
face in place.
FFU-HE/24/48/RSR/BC/ECM/115/10//CT//HEPA//ECMDX//WK/DSW/PC/TMB/ATS/ML/FL/WPF/PL-AL/F-AL/PL-B12/F-B12
NOTE:
Safety cables will be attached to the diffuser face, but care should be taken to ensure that diffuser face does not swing and
injure anyone.
If unit is bench top removable (BTR), proceed to next step.
STEP 2: Remove threaded plug covering ATS port using a 5/16" hex screw driver.
UNIT PORT LOCATIONS
STEP 3: Insert aerosol test fitting or adaptor (the aerosol injection port has a 3/8" NPT internal thread) into Aerosol Injection port.
NOTE:
An adaptor/test fitting that is longer than 1.5" and/or wider than 1" will not fit.
STEP 4: Inject aerosol test agent and measure particulate counts according to local codes.
NOTE:
Aerosol Sample port can be used to measure upstream particle counts. Refer to page 15 for static pressure port details.
STEP 5: Disconnect test equipment, and reinstall plugs in the static pressure (if applicable) and aerosol injection ports. Reinstall
diffuser face (if applicable).
If the safety cables were also disconnected when removing the face, they must be reattached. When reinstalling the face, care
should be taken to tuck safety cables in place without damaging the filter.
NOTE:
Airflow and aerosol challenge concentration should be kept uniform during the test. Static pressure and concentration may
be sampled through the static pressure port during the test, if required, to verify flow and concentration.
KNIFE EDGE
ATS PORT
STATIC PRESSURE
PORT
DIFFUSER FACE
priceindustries.com | FAN FILTER UNIT - Manual
FRAME
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ffu-he-rsr-fc

Table of Contents