Ecmdx - Price FFU series Installation And Service Manual

Fan filter unit
Hide thumbs Also See for FFU series:
Table of Contents

Advertisement

FAN FILTER UNIT
INSTALLATION & SERVICE INSTRUCTIONS

ECMDX

STEP 1: Determine Local Set-point from the formula based on the desired airflow using the appropriate chart below.
Constant Flow – Clean Filters (Forward Curved)
Voltage
Velocity
Volt
FPM
115
45-135
240
45-135
277
45-135
Voltage
Velocity
Volt
FPM
115
45-135
240
45-135
277
45-135
Constant Torque – Clean Filters (Backwards Curved)
Voltage
Velocity
Volt
FPM
115
45-135
240
45-135
277
45-135
Voltage
Velocity
Volt
FPM
115
45-135
240
45-135
277
45-135
Constant Torque – Clean Filters (Forward Curved)
Voltage
Velocity
Volt
FPM
45-90
Lset = (CFM/10.87) - 13
115
90-135
45-90
Lset = (CFM/10.82) - 13
240
90-135
45-90
277
90-135
Voltage
Velocity
Volt
FPM
45-90
115
90-135
45-90
240
90-135
45-90
277
90-135
24x24
BTR - FC
Lset = (CFM/3.35) - 44
Lset = (CFM/3.38) - 42
Lset = (CFM/3.31) - 43
BTR - FC
Lset = (CFM/6.94) - 42
Lset = (CFM/6.91) - 42
Lset = (CFM/6.97) - 41
24x24
BTR - BC
Not Available
Not Available
Not Available
BTR - BC
Lset = (CFM/17.03) - 16
Lset = (CFM/16.09) - 18
Lset = (CFM/15.68) - 19
24x24
BTR/FC
Lset = (CFM/7.26) - 26
Lset = (CFM/7.27) - 26
Lset = (CFM/9.93) - 15
Lset = (CFM/7.26) - 26
BTR/FC
Lset = (CFM/11.84) - 17
Lset = (CFM/7.43) - 48
Lset = (CFM/11.78) - 17
Lset = (CFM/7.42) - 48
Lset = (CFM/11.74) - 17
Lset = (CFM/7.33) - 49
RSR - FC
Lset = (CFM/2.33) - 46
Lset = (CFM/2.33) - 46
Lset = (CFM/2.35) - 42
24x48
RSR - BC
Not Available
Not Available
Not Available
24x48
RSR/FC
Lset = (CFM/10.23) - 11
Lset = (CFM/7.72) - 18
Lset = (CFM/11.28) - 8
Lset = (CFM/7.84) - 17
Lset = (CFM/10.32) - 10
Lset = (CFM/7.71) - 18
24x48
24x36
BTR - FC
Lset = (CFM/5.03) - 44
Lset = (CFM/5.06) - 44
Lset = (CFM/5.08) - 43
RSR - FC
Lset = (CFM/5.42) - 42
Lset = (CFM/5.45) - 41
Lset = (CFM/5.37) - 41
24x36
BTR - BC
Lset = (CFM/15.74) - 14
Lset = (CFM/15.78) - 14
Lset = (CFM/15.56) - 14
RSR - BC
Lset = (CFM/18.1) - 12
Lset = (CFM/18.28) - 12
Lset = (CFM/17.92) - 12
24x36
BTR/FC
Lset = (CFM/10.93) - 15
Lset = (CFM/6.78) - 41
Lset = (CFM/11.3) - 13
Lset = (CFM/6.92) - 39
Lset = (CFM/11.02) - 16
Lset = (CFM/7.74) - 33
RSR/FC
Lset = (CFM/12.86) - 13
Lset = (CFM/7.82) - 37
Lset = (CFM/12.72) - 13
Lset = (CFM/7.86) - 36
Lset = (CFM/12.79) - 12
Lset = (CFM/7.67) - 38
priceindustries.com | FAN FILTER UNIT - Manual
RSR - FC
Lset = (CFM/4.13) - 38
Lset = (CFM/4.06) - 39
Lset = (CFM/4.12) - 37
RSR - BC
Lset = (CFM/15.29) - 12
Lset = (CFM/13.76) - 15
Lset = (CFM/13.99) - 14
RSR/FC
Lset = (CFM/10.73) - 15
Lset = (CFM/8.12) - 25
Lset = (CFM/11.58) - 12
Lset = (CFM/8.75) - 22
Lset = (CFM/11.12) - 14
Lset = (CFM/7.92) - 26
37