IMPORTANT! Read and save these instructions. This manual to be left with the equipment.
INSTALLATION MANUAL
Ultrasonic Humidifier
US-Series
Humidification and Evaporative Cooling

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the US-Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Condair US-Series

  • Page 1 IMPORTANT! Read and save these instructions. This manual to be left with the equipment. INSTALLATION MANUAL Ultrasonic Humidifier US-Series Humidification and Evaporative Cooling...
  • Page 2 WARNING May present health risk if not maintained as instructed. Peut présenter un risque pour la santé si l'entretien n'est pas effectué conformement au mode d'emploi. Riesgo para la salud si no se siguen las instrucciones de mantenimiento.
  • Page 3 IMPORTANT! Read and save these instructions. This manual to be left with the equipment. INSTALLATION MANUAL Ultrasonic Humidifier US-Series Humidification and Evaporative Cooling...
  • Page 4 Liability Notice Condair Ltd. does not accept any liability due to incorrect installation, maintenance or operation of the equipment, or due to the use of parts/components/equipment that are not authorized by Condair Ltd.. Copyright Notice Copyright 2018, Condair Ltd., All rights reserved.
  • Page 5: Table Of Contents

    CONTENTS Introduction Before You Start General 1.2.1 Limitations of the Manual 1.2.2 Symbols Used in This Manual 1.2.3 Storage of Manual 1.2.4 Available Manuals and Languages Receiving and Storage 1.3.1 Inspection 1.3.2 Storage, Packaging, and Transportation Safety Precautions Compliance For Your Safety Hygiene Important Notes on Hygiene Hygiene Risk Management...
  • Page 6 Humidity Control Systems 7.5.1 Control Device Locations 7.5.2 Permissible Control Signal Inputs Best Practices 7.6.1 Remote Ultrasonic Blower Pack Installation Installation 7.7.1 Safety 7.7.2 Cleaning 7.7.3 Mounting the Humidifier 7.7.3.1 Mounting Checklist 7.7.4 Connecting the Water Supply 7.7.4.1 Water Supply Connections Checklist 7.7.5 Connecting the Drain Line 7.7.5.1 Drain Line Connections Checklist...
  • Page 7: Introduction

    If you have additional questions, please contact your Condair representative. They will be glad to assist you.
  • Page 8: Available Manuals And Languages

    Check the goods against the packing slip to ensure that all items have been delivered. Report any shortages to your Condair representative within 48 hours of receipt of the goods. Condair does not assume responsibilities for any shortages beyond this period.
  • Page 9: Safety Precautions

    Follow all local guidelines and regulations regarding the installation and operation of the unit; this includes (and not limited to) mounting, plumbing, water, gas, ventilation, and electrical connections. Please consult your local Condair representative to learn more. Introduction | 9...
  • Page 10: For Your Safety

    Requirements" on page 27 for details. Any other type of application, without the express written consent of Condair, is considered to be NOT conforming to its intended purpose, and may lead to dangerous operation and will void the warranty. In order to operate the equipment in the intended manner all information contained in this manual, in particular the safety instructions, must be observed closely.
  • Page 11 CAUTION! Electrostatic discharge (ESD)! The electronic components inside the control cabinet in the humidifier are sensitive to elec- trostatic discharge (ESD). Prevention: Take appropriate measures to protect the electronic components inside the unit against damage caused by electrostatic discharge (ESD). Refer to ANSI/ESD-S20.20. WARNING! Heavy object.
  • Page 12 Modifications to the Unit Prohibited Modifications are NOT permitted on the Ultrasonic Humidifier without the express written consent of Condair. Safety Labels The safety label (hygiene) is found on the right wall inside the plumbing cabinet (on the panel sep- arating the electrical cabinet).
  • Page 13: Hygiene

    There are multiple points in the humidification system where a contamination can occur. It is the responsibility of the customer and of Condair to ensure that health hazards due to contamination are reduced to acceptable levels. The use of a hygiene risk assessor is recommended.
  • Page 14: Guidelines To Keep A Clean System And Prevent Micro-Organism Growth

    Repair and fault finding. Training and guidance. Note: * Condair uses a quick method for measuring bacterial activity in the water with the use of BactiQuant (BQ). Once the water sample has been taken, the bacteriological quality of the water is read within 30 minutes, and the Condair service team will disinfect the system if necessary.
  • Page 15: Product Description

    Product Description General Description The Ultrasonic Humidifier is a steam-less humidifier. To humidify the space, the Ultrasonic Humidifier creates mist using piezoelectric transducers. Mist is expelled from the unit with internal fans, and an Ultrasonic Blower Pack (if installed), into the space. Mist is then absorbed into the air. The Ultrasonic Blower Pack comes in 4 different output capacities;...
  • Page 16: Options

    Treated water enters the humidifier's reservoir from an inlet located at the bottom of the unit. The water that enters the humidifier's reservoir must be treated to remove minerals, bacteria and fungi, and should otherwise be pure to prolong the service cycle of the unit and, above all, safeguard the public. An accu- mulation of minerals will result in scale, and an accumulation of bacteria and fungi will result in unhygienic conditions in the space.
  • Page 17 Table 2: Ultrasonic Humidifier Accessories Accessory Application Disinfection kit Disinfecting and cleaning kit. (PN: 2594996) Air filter kit, humidifier Replacement air intake filter(s) for the humidifier. (PN: 2594401 US 7-20) (PN: 2594995 US 40) Air filter kit, blower pack Replacement air filters for the Ultrasonic Blower Pack. (PN: 2588764) Manuals (PN: 2588786 Installation Manual)
  • Page 18: Product Specifications

    Product Specifications Technical Data 5.1.1 Capacity Table 3: Ultrasonic Humidifier Capacity Capacity Model Housing Size at 120V/208/240V/1 Mist Production Power Rating US 7 Medium 3 kg/h (6.6 lb/h) 250 W US 13 6 kg/h (13.2 lb/h) 250 W US 20 9 kg/h (19.8 lb/h) 650 W US 40*...
  • Page 19: Dimensions

    5.1.3 Dimensions Table 7: Ultrasonic Humidifier Dimensions (excludes flexible tubes) Model Housing Dimensions height x width x depth US 7 Medium 780 x 530 x 406 mm US 13 (30.71 x 20.87 x 15.96 in) US 20 US 40 Large 780 x 1000 x 406 mm (30.71 x 39.37 x 15.96 in) Table 8: Ultrasonic Blower Pack Dimensions...
  • Page 20 Table 9: Ultrasonic Humidifier, Maximum External Fusing — Single-Phase Mod- 110-120V/1~ 208V/1~ 220-240V/1~ Max- Max- Max- Max- Max- Max- Max- Max- Max- imum imum imum imum imum imum imum imum imum Output Cur- External Output Cur- External Output Cur- External rent Dis- rent...
  • Page 21: Specification Drawings

    Specification Drawings Figure 2 - Specification Drawing Medium Housing ( US 07-20) A. 405.4 mm (15.96 in) E. 54 mm (2.13 in) I. 204.6 mm (8.05 in) B. 780 mm (30.71 in) F. 89.7 mm (3.53 in) J. 96.5 mm (3.8 in) C.
  • Page 22 Figure 3 - Specification Drawing Large Housing ( US 40) A. 75 mm (2.95 in) I. 590 mm (23.23 in) Q. 97 mm (3.82 in) B. 91.5 mm (3.60 in) J. 263.5 mm (10.37 in) R. 205 mm (8.07 in) C.
  • Page 23: Installation And Planning

    Observe and comply with all local and national codes dealing with water and electrical installations. Condair does not accept any liability for installation of humidification equipment by unqualified personnel, or the use of equipment and parts that are not authorized by Condair.
  • Page 24: Installation Overview

    The Ultrasonic Humidifier runs optimally with treated water, such as RO water (recommended) and DI water (see Condair representative). A typical installation will have an RO-U System with buffer tank. Refer to the Reverse Osmosis System Installation, Operation, and Maintenance Manual (P/N: 2594385_A_EN_1811_RO_IOM).
  • Page 25 25 | Installation and Planning 2588786_A_EN_1811_US_IM...
  • Page 26: Location Requirements

    The clearances shown in Figure 5 - on the next page are for reference only, and are suggested for ease of maintenance. Consult local installation codes. Condair does not accept responsibility for viol- ations of installation codes. Installation and Planning | 26...
  • Page 27: Site Requirements

    Figure 5 - Suggested Clearances Ultrasonic Humidifier 1. Direct-mount installation 2. Remote-mounted installation Note: The value E for a direct-mounted installation is zero because the Ultrasonic Blower Pack is moun- ted directly onto the humidifier. Table 10: Mounting Clearances for Ultrasonic Humidifier Dimensions US 7, 13, 20 US 40...
  • Page 28: Flexible Tube Requirements

    Do NOT mount the humidifier on: on hot surfaces on surfaces that freeze on the floor near vibrating components 7.4.2 Flexible Tube Requirements An optional kit is available (see Ultrasonic Humidifier Spare Parts List) that contains a 2 m (78 in) flexible tube.
  • Page 29 (D.I.), and should be free of additives, such as corrosion inhibitors, and disinfectants, which may affect the performance of the humidifier. Note: If using softened water, contact your Condair representative for assistance. The water supply should have a minimum flow rate of 3.3 L/min (0.9 gpm).
  • Page 30 * If the water entering the RO-U system is greater than the values indicated in this table, install a water softener between the water supply and the Reverse Osmosis System. ** Contact your Condair representative if the conductivity of the supply water is greater than 350 µS/cm. Installation and Planning | 30...
  • Page 31: Drainage Requirements

    < 200 CFU/ml for industrial applications** follow applicable regulations * if the conductivity of the water entering the RO-U system is greater than 350 µS/cm, contact your Condair rep- resentative . ** CFU leaving the unit via mist should be <1000 CFU/ml for industrial applications. Keep the CFU entering the humid- ifier as low as possible, such that the CFU leaving the unit is within acceptable guidelines.
  • Page 32: Humidity Control Systems

    The power supply must have an external dedicated fused disconnect switch (supplied by oth- ers). The fusing must not exceed the maximum circuit protection indicated on the specification label. Refer to "Model Designation" on page 15. Humidity Control Systems 7.5.1 Control Device Locations The following schematic describes a potential system set-up with respect to control devices.
  • Page 33: Best Practices

    7.6.1 Remote Ultrasonic Blower Pack Installation Use Condair flexible tubes that are provided by your Condair representative. Mist connection materials from another manufacturer may adversely affect the operation of the unit. The length of the mist line should be kept as short as possible. It should not exceed the max- imum equivalent length of 2 m (6.56 ft).
  • Page 34 (full demand to mist; zero stop mist and allow to drain). Condair provides a cleaning and disinfecting kit for the Ultrasonic Humidifier (P/N: 2594996) IMPORTANT! Avoid cleaning with hard or rough materials, such as steel wool, or metal brushes. Abra- sions on the surface of any components may prevent micro-organisms from being cleaned easily.
  • Page 35: Mounting The Humidifier

    5. Rinse the hoses with clean water (RO or DI water) to remove residue from disinfectant. 7.7.3 Mounting the Humidifier Refer to "Mounting Requirements" on page 27 for mounting requirements. Figure 9 - Lag Bolt Hole Locations for Medium and Large Condair US 35 | Installation and Planning 2588786_A_EN_1811_US_IM...
  • Page 36: 7.7.3.1 Mounting Checklist

    1. Rear view of medium Ultrasonic Humidifier 2. Rear view of large Ultrasonic Humidifier 3. Clearance from the mounting surface at point A, 5 mm (0.25 in) 4. Screw (not supplied) Table 12: Mounting Screw Spacing X and Y Medium US 7-20 407 mm (16 in) 526 mm (20.7 in) Large US 40...
  • Page 37: 7.7.4.1 Water Supply Connections Checklist

    Figure 10 - Water Supply Connections 1. Water supply inlet 2. Adapter* , 3/4 in BSPP to 1/2 in NPT (supplied) 3. Water supply line * Hand-tighten the adapter to the inlet valve. 7.7.4.1 Water Supply Connections Checklist Water Supply Connection □...
  • Page 38: 7.7.5.1 Drain Line Connections Checklist

    Figure 11 - Drain Line Connections 1. Hose clamp (supplied) 2. Flexible bent hose (supplied) 3. Drain line, minimum inner diameter 22 mm (7/8 in) (not supplied) 4. Air gap funnel, minimum 64 mm (2-1/2 in) (not supplied) 5. Trap, minimum diameter 40 mm (1.57 in) (recommended, not supplied) 6.
  • Page 39: Connecting The Flexible Tubes

    7.7.6 Connecting the Flexible Tubes IMPORTANT! For proper installation of the flexible tubes, ensure that the "Flexible Tube Requirements" on page 28 are met. IMPORTANT! Use gloves and keep the system clean during installation. 1. Open the humidifier cabinet. 2. Remove the clamp from the flexible tube. This will allow the flexible tube to pass through the top of the humidifier cabinet.
  • Page 40: 7.7.6.1 Flexible Tube Connections Checklist

    7.7.6.1 Flexible Tube Connections Checklist □ Flexible tubes cleaned? □ The length of flexible tubes must be kept as short as possible □ Flexible tubes should allow condensate to flow back to the humidifier (otherwise, use con- densate traps for drainage along the connection) 7.7.7 Connecting the Ultrasonic Blower Pack The Ultrasonic Blower Pack can be installed remotely, or directly on the Ultrasonic Humidifier (medium...
  • Page 41 DANGER! Risk of electric shock! The unit is mains powered. Using the On/Off switch on the humidifier to shut down the unit will NOT shut off power to the control cabinet. Live parts may be exposed when the access panels or doors are removed.
  • Page 42: 7.7.9.1 Installing External Electrical Connections

    7.7.9.1 Installing External Electrical Connections The different external connections to the Ultrasonic Humidifier are: "Power Supply Connection (Single-Phase)" below "External Safety Chain" on the next page "Modulating Demand or Humidity Signal" on the next page "Ohmic Humidity Controller (Passive)" on page 44 "24 VDC On/Off Humidistat"...
  • Page 43 inet. Refer to Figure 14 - on the previous page. 6. Reinstall and secure the door panels once the electrical connections are complete. External Safety Chain The potential-free contacts of external monitoring devices (ventilation interlock, safety high limit humidistat, airflow monitor, etc.) are connected to safety chain, K2, of the XE2 terminal block. Refer to Appendix: "Wiring Diagram Ultrasonic Humidifier - Medium"...
  • Page 44 + – 1 2 3 4 5 6 7 8 9 Figure 16 - Modulating Demand or Humidity Signal Connection 1. Control cabinet 2. External 3. Driver board 1. Open the door panels to access the control cabinet of the Ultrasonic Humidifier. 2.
  • Page 45 Ω Ω ...10k 1 2 3 4 5 6 7 8 9 Figure 17 - Ohmic Humidity Controller Connection 1. Control cabinet 2. External 3. Driver board 1. Open the door panels to access the control cabinet of the Ultrasonic Humidifier. 2.
  • Page 46 On/Off 1 2 3 4 5 6 7 8 9 Figure 18 - On/Off Humidistat Connection 1. Control cabinet 2. External 3. Driver board 1. Open the door panels to access the control cabinet of the Ultrasonic Humidifier. 2. Ensure that the main power cable is properly grounded through the ground lug inside the control cabinet.
  • Page 47: 7.7.9.2 Electrical Connections Checklist

    7.7.9.2 Electrical Connections Checklist □ Power supply meet the voltage and current requirements shown on the specification label? Refer to "Model Designation" on page 15. □ Power supply have an external dedicated fused disconnect? □ Unit is using the correct external fusing? Refer to "Maximum External Fusing".
  • Page 48: Humidification Load Calculations

    For a straight, vertical flexible tube of length 2 m (6.6 ft), expect a 20% reduction in output capacity. The addition of angles in the flexible tube connection will decrease the output further. Please contact your Condair representative for more information on calculating mist losses. Humidification Load Calculations | 48...
  • Page 49: Commissioning

    First-time Commissioning The unit must always be commissioned for the first time by a service technician from your Condair rep- resentative, or by personnel who are well trained and authorized by the customer. For this reason, this manual only provides an outline, and not the details of the commissioning protocol.
  • Page 50 APPENDIX Appendix 2588786_A_EN_1811_US_IM...
  • Page 51: A Appendix

    A                 Appendix: Installation Checklist Mounting □ Unit installed in a suitable location? Refer to "Location Requirements" on page 26. □ Unit installed with suitable clearances? Refer to "Clearance Requirements" on page 26. □ Mounting surface is stable and capable of supporting the full operating weight of the unit? Refer "Weights"...
  • Page 52 Electrical Connection □ Power supply meet the voltage and current requirements shown on the specification label? Refer to "Model Designation" on page 15. □ Power supply have an external dedicated fused disconnect? □ Unit is using the correct external fusing? Refer to "Maximum External Fusing".
  • Page 53: B Appendix

    B                 Appendix: Wiring  Diagram Ultrasonic Humidifier - Reservoir MU-6 MU-3 MU-5 MU-2 MU-4 MU-1 LEVEL SWITCH MAIN 1 2 3 4 5 6 7 8 1 2 3 4 MU4-6 MU1-3 Figure 19 - Wiring Diagram of the Ultrasonic Humidifier Reservoir Wiring Diagram Ultrasonic Humidifier - 2588786_A_EN_1811_US_IM Reservoir | 53...
  • Page 54 Legend CN1: Misting unit power input T1-T12: Transducers Internal fuse 48V (3.15mA, slow acting) Level, temperature and fan connection MU1-MU6: Misting unit boards Misting units power connection Wiring Diagram Ultrasonic Humidifier - 2588786_A_EN_1811_US_IM Reservoir | 54...
  • Page 55: C Appendix

    C                 Appendix: Wiring  Diagram Ultrasonic Humidifier - Medium GNYE PSU1 PSU3 PSU2 SMPS SMPS ON/OFF SWITCH SMPS 24VDC/75VA 24VDC/100VA 48VDC/600VA -V +V +V -V 230VAC/50Hz To CN3 110...240V 50/60Hz (BLOWERCONTROL) UHUV-10 CN10 CN12 CN15 GND SPARE G ND DRAIN G ND INLET...
  • Page 56 Legend Internal fuse 24 V supply (315 mA, slow acting) Jumper, do not remove Jumper, do not remove PSU1: Power supply 24 VDC 50 VA PSU2: Power supply 48 VDC 600 VA On/Off switch Rotary switch module identification: 0 Level, temperature and fan connection Missing units power connection XE1: Supply voltage terminal block...
  • Page 57: D Appendix

    D                 Appendix: Wiring  Diagram Ultrasonic Humidifier - Large (A-unit) GNYE PSU1 PSU3 A- unit PSU2 SMPS SMPS ON/OFFSWITCH SMPS 24VDC/75VA 24VDC/100VA 48VDC/600VA -V +V +V -V 230VAC/50Hz To CN3 110...240V 50/60Hz (BLOWERCONTROL) - D R AIN M odule B To CN7 (double unit only)
  • Page 58 Legend Internal fuse 24 V supply (315 mA, slow acting) Jumper, do not remove Jumper, removed on driver board A, installed on driver board B PSU1: Power supply 24 VDC 50 VA PSU2-PSU3: Power supply 48 VDC 600 VA On/Off switch Rotary switch module identification: 0 Level, temperature and fan connection Missing units power connection...
  • Page 59: E Appendix

    E                 Appendix: Wiring  Diagram Ultrasonic Humidifier - Large (B-unit) GNYE PSU1 PSU3 -unit PSU2 SMPS SMPS ON/OFFSWITCH SMPS 24VDC/75VA 24VDC/100VA 48VDC/600VA -V +V +V -V To CN3 (BLOWERCONTROL) To X0-A To Drain B(Battery Pack) UHUV-10 CN10 CN12...
  • Page 60 Legend Internal fuse 24 V supply (315 mA, slow acting) Jumper, do not remove Jumper, removed on driver board A, installed on driver board B PSU1: Power supply 24 VDC 50 VA PSU2-PSU3: Power supply 48 VDC 600 VA On/Off switch Rotary switch module identification: 0 Level, temperature and fan connection Missing units power connection...
  • Page 61 Notes:...
  • Page 62 Warranty Condair Inc. and/or Condair Ltd. (hereinafter collectively referred to as THE COMPANY), warrant for a period of two years after installation or 30 months from manufacturer’s ship date, whichever date is earlier, that THE COMPANY’s manufactured and assembled products, not otherwise expressly war- ranted, are free from defects in material and workmanship.
  • Page 63 CONSULTING, SALES, AND SERVICE: U.S.A. 826 Proctor Avenue Ogdensburg, NY 13669 CANADA 2740 Fenton Road Ottawa, ON, K1T 3T7 Tel: 1.866.667.8321 Fax: 613.822.7964 Email: na.info@condair.com Website: www.condair.com...