Page 1
Read and save these instructions. This manual to be left with the equipment. OPERATION MANUAL Steam humidifier Condair RS II Humidification, Dehumidification and Evaporative Cooling...
Page 2
Condair Ltd., except to the extent required for installation or maintenance of recipient's equipment. Liability Notice Condair Ltd. does not accept any liability due to incorrect installation or operation of the equipment or due to the use of parts/components/equipment that are not authorized by Condair Ltd.
For your safety Product Overview Construction Condair RS steam humidifier Functional description System overview Condair RS for duct humidification System overview Condair RS for direct room humidification Operation First-time commissioning Display and operating elements Commissioning after an interruption of operation Notes on operation 4.4.1...
Page 4
Important notes on maintenance Maintenance intervals Maintenance list Removing and installing components for maintenance 6.4.1 Preparing the Condair RS for the removal of components 6.4.2 Removal and installation of the scale collector tank 6.4.3 Removal and installation of the steam cylinder 6.4.4...
To the very beginning We thank you for having purchased the Condair RS steam humidifier. The Condair RS steam humidifier incorporates the latest technical ad van ces and meets all recognized safety standards. Nevertheless, improper use of the Condair RS steam humidifier may result in danger to the user or third parties and/or damage to property.
Page 6
Please safeguard this operation manual in a safe place, where it can be immediately accessed. If the equipment changes hands, the documentation must be passed on to the new operator. If the documentation gets misplaced, please contact your Condair representative. Introduction...
Condair RS safely and correctly. All icons, signs and markings applied to the components of the Condair RS must be observed and kept in readable state.
Page 8
Condair RS is no longer operating correctly – if connections and/or piping are not sealed All persons working with the Condair RS must report any alterations to the unit that may affect safety to the owner without delay. Prohibited modifications to the unit No modifications must be undertaken on the Condair RS without the express written consent of Condair.
Functional description The Condair RS steam humidifier is an atmospheric steam generator. It operates on the resistance heating principle and is designed for direct room air humidification (with blower pack) and indirect humidification (with steam distributor) in venti lating and air-conditioning systems.
12 Air proving switch 13 Steam distributor 14 Humidity controller or humidity sensor 15 High limit humidistat Fig. 2: System overview Condair RS for duct humidification Note: For units equipped with RS-RO option, refer to Fig. 2611995-0 EN 2408 Product Overview...
13 Humidity controller or humidity sensor 14 High limit humidistat Z261 Fig. 3: System overview Condair RS for direct room humidification (blower pack shown in "built on" and "remote" configurations) Note: For units equipped with RS-RO option, refer to Fig.
Operation The Condair RS steam humidifier may be commissioned and operated only by persons familiar with the Condair RS steam humidifier and adequately qualified. It is the owner’s responsibility to verify proper qualification of the personnel. First-time commissioning The first-time commissioning must always be done by a service technician of your Condair representative or a well trained and authorized person of the customer.
7.2). If the function check on the level unit is successful, the Condair RS will be in normal operating mode and the home screen is shown. The heating current switches on as soon as the humidity controller/ humidistat demands humidity. The LED lights green and steam is produced after a short delay.
Notes on operation 4.4.1 Inspections during operation During operation the Condair RS and the humidification system have to be inspected weekly. On this occasion check the following: • the water and steam installation for any leakage. • the steam humidifier and the other system components for correct fixing and any damage.
In order to stop the drain cycle, press the <Cancel> button in the drain progress window. The drain cycle is stopped, and the home screen is shown again. 5. If you have to carry out work on the Condair RS, switch off steam humidifier via the unit switch. Otherwise the steam cylinder(s) is/are immediately filled again.
Taking the unit out of operation In order to take the Condair RS steam humidifier out of operation (e.g. for maintenance purpose), per- form the following steps: 1. Close the shut-off valve in the water supply line. 2. If applicable: Stop the RO-E pure water system according to the separate Condair RO-E installation and operation manual.
Operating the Condair RS control software Home screen After switching on the Condair RS and the automatic system test has been passed the Condair RS is in normal operating mode and the home screen is shown. Note: The appearance of the home screen depends on the current device and error status and the con- figuration of the humidity/temperature control of the system.
Device Status Cyl. A/B: Shows the current status 18:04 18:04 02.04.2024 02.04.2024 of steam cylinder A and B of the Condair RS. Home Status Note: Device Status Cyl. B only appears on large Device Status Cyl. A and double units.
Page 20
Description Initializing The control is initializing. Stopped The Condair RS was stopped due to a malfunction that makes it impossible to continue operation. Standby No humidity demand for more than 60 minutes the Condair RS is in standby mode. Humidifying The Condair RS is producing steam (humidifying).
Note: This setting appears if signal source is set to "BACnet". – Setpoint: Setting of the desired humidity setpoint 18:04 18:04 02.04.2024 02.04.2024 value in %rh. Home Setpoint Standby 41 % Humidity 1685 hr Next Maintenance Winterzeit 2611995-0 EN 2408 Operating the Condair RS control software...
– Next Small Maintenance Cyl. A/B : Shows the Next Small Maintenance remaining time in hours until the small mainte- 464 h nance of steam cylinder A/B of the Condair RS is due. Next Small Maintenance 464 h Demand –...
Query operating states in the "About" submenu – Humidifier Model: Shows the humidifier model selected ("RS" = Condair 18:04 02.04.2024 RS only or "RS-RO" = Condair RS with optional Condair RO-E pure water About system). Humidifier Model – RS Type: Shows that Condair RS is configured as process unit ("Op- RS-RO tion P").
"8808" must first be entered before the setting dialog for the parameter appears. Quick access number 18:04 18:04 18:04 02.04.2024 02.04.2024 02.04.2024 Help Quick Access Language About English Quick Access Deutsch Contact Data Français Condair Ltd. Italiano info@condair.com www.condair.com Español 1001 Operating the Condair RS control software 2611995-0 EN 2408...
Region Options: different languages Language Units: With this setting you determine the desired unit system. – English Factory setting: depending on the country Units Imperial Options: Metric or Imperial 2611995-0 EN 2408 Operating the Condair RS control software...
USB interface on the control board. After pressing the selection field, Load Parameters from... a confirmation dialog appears in which you have to confirm the loading of the parameter settings again. Operating the Condair RS control software 2611995-0 EN 2408...
Touchscreen Settings range: 15 ... 100 % 80 % – LED: With this setting you determine the desired value for the brightness of the status LED. 25 % Factory setting: 25 % Settings range: 25 ... 100 % 2611995-0 EN 2408 Operating the Condair RS control software...
Error/Warning Reset: With this function you can reset pending errors/ warnings after eliminating the malfunction(s). After pressing the selection field, a confirmation dialog appears in which you have to confirm the reset again. The Condair RS then restarts. Operating the Condair RS control software 2611995-0 EN 2408...
It may have to be adapted to the actual circumstances during operation. – Maintenance Mode: With this parameter you can set the maintenance 18:04 02.04.2024 mode for the Condair RS ("Small + Extended" or "Extended"). Water Management Factory setting: Small+Extended Water Mode Options:...
Page 30
– Maintenance Mode: With this parameter you can set the maintenance 18:04 02.04.2024 mode for the Condair RS ("Small + Extended" or "Extended"). Water Management Factory setting: Small+Extended Water Mode...
USB stick. Note: Before you carry out this function, you must insert a FAT32 format- ted USB stick into the USB interface on the control board. 2611995-0 EN 2408 Operating the Condair RS control software...
Export Log File: With this function you can save an error log file created by the control on a USB stick and send it to Condair for further analysis. Note: Before you carry out this function, you must insert a FAT32 format- ted USB stick into the USB interface on the control board.
10V Ext. Supply 9.8 V Note: If the Condair RS is operated together with a Condair RO-E pure water system, an additional submenu with input diagnostic functions is available for the RO-E pure water system. Please refer to the information in the separate operation manual for the Condair RO-E pure water system.
02.04.2024 Home Password Menu Features General Operation **** Standby Timers Maintenance Softstart Features Demand Desalt Controls 1685 hr Next Maintenance Standby Network 1001 Password: "8808" Standby Drain Options Ext. Pipe Flush Operating the Condair RS control software 2611995-0 EN 2408...
On or Off 5.3.3.3 Setup operation timers in the "Timers" submenu In the "Timers" submenu you can define up to 10 timers for timer controlled operation of the Condair RS. Ex factory all timers are deactivated. You can define timers for: –...
Page 36
06:00 Capacity Limitation (Condair RS operates with Mode the desired capacity limitation) Capacity Limitation Setpoint (Condair RS operates with the desired Capacity Limitation humidity setpoint) 100 % Note: The option "Setpoint" is only accessible if the "Control CH1 Mode" in "Controls > Control CH1" is set to "RH P" or "RH PI"...
Water Counts: With this setting you determine how many times the maximum level in the steam cylinder can be reached within one hour (foam detection) before a time-controlled flushing cycle will be initiated. Factory setting: Setting range: 1 ... 8 2611995-0 EN 2408 Operating the Condair RS control software...
5.3.3.6 Settings in the "Standby" submenu – Standby Mode: With this setting you determine the operational behaviour 18:04 02.04.2024 of the Condair RS in standby operation. Standby Factory setting: Idle Drain Standby-Mode Options: Idle Drain (the steam cylinder is drained and re-...
("Off") the optional drain valve for the automatic draining of the scale collector tank in standby operation. Note: if the optional drain valve is activated, the Condair RS is completely drained in standby operation (including scale collector tank) and refilled only after a humidity demand is present again.
5.3.4 Settings and features in the "Controls" submenu In the "Controls" submenu you determine the control settings for the Condair RS. The control settings available depend on the selected signal source and the control mode. Additionally you can determine the parameters for the operation of interconnected devices.
"Control Channels" in the signal settings submenu is set to "Dual". – Control CH1 Mode / Control CH2 Mode: With this setting you determine 18:04 02.04.2024 the type of controller used with the Condair RS steam humidifier. Control CH1 Factory setting: Demand Control CH1 Mode...
Page 42
Note: This setting only appears if "Control CH1 Mode" / "Control CH2 Mode" is set to "RH P" or "RH PI" and "RH Alert Mode" is activated ("On"). Factory setting: 20 % Options: 20 ... 95 % Operating the Condair RS control software 2611995-0 EN 2408...
Note: This setting appears only, if the "Sequence Rotation" function is activated ("On"). Factory setting: 24 hours Setting range: 24 ... 1000 hours 2611995-0 EN 2408 Operating the Condair RS control software...
02.04.2024 02.04.2024 Home Password Menu Network IP Settings **** Maintenance Standby IoT Settings Features Modbus Settings Controls Demand BACnet Settings 1685 hr Network Next Maintenance Remote Fault Indication 1001 Password: "8808" Operating the Condair RS control software 2611995-0 EN 2408...
Primary DNS 000.000.000.000 – IP Address: This field shows the actual IP address of Condair RS assigned manually or assigned by a DHCP server. Primary DNS If the parameter "DHCP Mode" is set to "Fixed", the IP address of Con- 000.000.000.000...
BACnet/IP (BACnet/IP via RJ45 interface) Important: regarding the setting of the individual BACnet parameters as well as the wiring of the Condair RS for the BACnet IP or BACnet MS/TP communication, please observe the instructions in the sepa- rate BACnet addendum manual. This manual can be requested from your Condair representative.
Safety Loop: With this setting you determine whether an Error ("Error") or Warning a Warning ("Warning") is triggered when the external safety loop is open. Factory setting: Warning Options: Warning or Error 2611995-0 EN 2408 Operating the Condair RS control software...
There is danger of burning when the steam cylinder(s) and the scale collector tank(s) is/are dismounted shortly after steam has been produced. Prevention: Before carrying out any work on the steam system set the Condair RS out of operation as described in chapter 4.5...
To maintain operational safety the Condair RS steam humidifier must be maintained at regular intervals. The control software of the Condair RS features two maintenance counters one for the "Small mainte- nance" (Cleaning of the scale collector tank, only for units equipped with a scale collector tank) and one for the "Extended maintenance"...
Visually inspect the elements for pitting, burn marks, corrosion, crack. Replace the defective elements immediately. Contactors Have the contactors be replaced by an electrician every 5 years or when the warning for contactor replacement appears. Contactors must be pur- chased from Condair. Maintenance 2611995-0 EN 2408...
6.4.1 Preparing the Condair RS for the removal of components Before starting any removal work set the Condair RS out of operation and drain the steam cylinder and the scale collector tank (if applicable). Proceed as follows: 1. Condair RS must be switched on. Perform a draining of the steam cylinder (see chapter 4.4.3).
6.4.2 Removal and installation of the scale collector tank Removal WARNING! Danger of burning! Before removal of the scale collector tank ensure it is empty and the temperature indication adhesive on the scale collector tank indicates a temperature <122 °F (<50°C). Snap ring O-ring Strainer...
Page 53
Installation Prior to the installation: • Check scale collector tank, O-ring, snap ring and strainer insert for damages and replace defective components if necessary. We recommend to replace the sealings of the scale collector tank with each maintenance. • Remove any dirt inside the retaining ring on the bottom of the unit and clean it with a clean rag. Snap ring O-ring Strainer...
6.4.3 Removal and installation of the steam cylinder WARNING! Danger of burning! Before removal of the steam cylinder ensure the steam cylinder is empty and has cooled down, that no more burning danger exists. 1. Loosen retaining screw on front door or on left front door (for large units) of the unit using a screw- driver, then remove the front door.
Page 55
CAUTION! Set down the steam cylinder carefully to ensure the funnel on the bottom side of the cylinder is not damaged! 4. Undo the steam cylinder cover clamping ring. 5. Carefully lift off the cover with the heating elements. CAUTION! Take care with the cover while it is removed, so as not to damage the heating elements.
Page 56
6. If necessary, loosen the funnel insert by lightly rotating it in either direction and lift it together with baffle from the steam cylinder. Then, remove the screen insert from the funnel insert. 7. If during maintenance one or more heating elements must be replaced: •...
Assembly and installation of the steam cylinder Assembly of the steam cylinder takes place in reverse sequence of the removal. Please note the fol- lowing instructions: – Installation of any heating elements which have been removed should follow the figure of step 7. Please take care that the heating elements are correctly positioned and the cables are correctly connected (according to your notes).
6.4.5 Removal and installation of the filling cup, the level unit and the water hoses For removing the filling cup, the level unit and the water hoses the steam cylinder must be removed first (see chapter 6.4.3). Drain water cooling hose Cable tie Support 1. Release hose clamps, then disconnect all hoses from the corresponding connectors and remove the hoses.
6.4.6 Removal and installation of the drain pump For removing the drain pump the steam cylinder must be removed first (see chapter 6.4.3). 1. Detach electric cables (polarity of the cables must not be observed). 2. Release hose clamps and remove the hoses from the connectors. 3.
6.4.7 Removal and installation of the inlet valve and the optional secondary inlet valve For removing the inlet valve the steam cylinder must be removed first (see chapter 6.4.3). Single inlet valve Double inlet valve Secondary inlet valve (RS-RO option) 1.
6.4.8 Removal and installation of the steam cylinder receptacle For removing the steam cylinder receptacle the steam cylinder must be removed first (see chapter 6.4.3). 1. Release hose clamps and remove hoses from the connectors. 2. Undo the screw fixing cylinder receptacle to the bottom of the housing with Phillips screwdriver. 3.
Notes on cleaning the unit components Unit component What to clean and how to clean Scale collector tank • Dump any lime in scale collector tank, then carefully remove any limescale inside scale collector tank and on the strainer insert using a soft bristled brush (do not use a wire brush).
Page 63
Unit component What to clean and how to clean Hoses • Loosen any limescale in the hoses by carefully twisting and flexing the hoses, then flsuh out the hoses thoroughly with hot water. Inlet valve • Carefully remove any limescale inside the inlet valve(s) and on the strainer(s) using a soft bristled brush (do not use a wire brush).
Unit component What to clean and how to clean Drain cup • Carefully remove any limescale from the drain cup and its connectors using a soft bristled brush (do not use a wire brush). • Wash the drain cup and the receptacle on the bottom side of the unit with a lukewarm soap solution, rinse the parts well with tap water.
Resetting the maintenance counter After completing the "Small maintenance" or the "Extended maintenance", the corresponding mainte- nance indication or maintenance counter (for module A or module B or for both), respectively must be reset. Proceed as follows to reset the maintenance counter: 18:04 18:04 18:04...
Performing a software update To update the control software or the driver board firmware, proceed as follows: 1. Set the On/Off switch on the front side of the steam humidifier to the Off position, then switch off the voltage supply to the steam humidifier via the external electrical isolator and secure switch in the off position to prevent it from inadvertent power up.
General notes Only use original spare parts from your Condair representative to replace defective parts. Safety Before starting repair work on the Condair RS set the unit out of operation and disconnect it from the mains (see chapter 4.5).
Fault indication Malfunctions during operation detected by the control software are indicated by a corresponding Warn- ing message (Status LED lights up yellow and the exclamation mark symbol is displayed in the device and error status field of the home screen) or Error message (Status LED lights up red and the cross symbol is displayed in the device and error status field of the home screen).
(e.g. hose connections, humidity control system, etc.). Note: Remedial measures highlighted in gray in the malfunction list may only be remedied by a Condair service technician or a service center authorized by Condair. If applicable, contact your Condair repre- sentative.
Page 70
Possible causes Remedy Safety Loop External safety loop is open. Humidification is stopped! Note: as soon as the safety loop is closed again the Condair RS continues to work normally. Ventilation interlock open. Check/switch on fan of the AHU. Air proving switch has triggered.
Page 71
No water level detected with security floater while operation floater detected a water level. Humidification is stopped! Note: As soon as the level is within the valid range again, the Condair RS con- tinuous normal operation. Magnetic field in vicinity of level unit.
Page 72
––– Heating voltage Heating voltage is missing although a demand is present. missing Note: As soon as the heating voltage is present again, the Condair RS continu- ous normal operation. Main contactor defective. Contact your Condair representative. Phase failure heating voltage supply.
Page 73
Maximum The maximum vaporization time has exceeded. v aporization time Note: If the maximum vaporization time is exceeded the Condair RS carries out a exceeded level test. This procedure is repeated three times if maximum vaporization time is exceeded again, then a fault message is triggered and humidification is stopped! Individual heating elements faulty.
Page 74
Contact your Condair representative.. cycles of the relays on the driver board has been reached. These fault messages must be reset via the control software or by switching the Condair RS off and on again (see Section 7.6) Fault elimination...
Fault behavior of units in a device interconnected system Fault in the main unit If a fault occurs on the main unit that is relevant to the system (e.g. request signal interrupted, external safety chain open, etc.), a fault is displayed on the main unit and all units in the device interconnected system are stopped.
Saving fault and service histories to a USB memory stick The fault and service histories of the Condair RS can be saved to a USB memory stick for logging and further analysis. For this purpose proceed as follows: 1. Set the On/Off switch on the front side of the steam humidifier to the Off position, then switch off the voltage supply to the steam humidifier via the external electrical isolator and secure switch in the off position to prevent it from inadvertent power up.
Resetting malfunction indication To reset the malfunction indication, proceed as follows: 18:04 18:04 18:04 18:04 02.04.2024 02.04.2024 02.04.2024 02.04.2024 Home Password Menu Maintenance General Reset **** Standby Maintenance Settings Water Management Features Demand Update Controls 1685 hr Next Maintenance Histories Network 1001 Password: "8808"...
Fig. 7: Position of the backup battery and the fuses on the driver board 5. Swivel control board assembly 90°inwards. 6. Relocate front cover on control unit and lock it with the retaining screw. 7. Reconnect Condair RS to the mains by switching on the electrical isolator.. Fault elimination 2611995-0 EN 2408...
Taking out of service/Disposal Taking out of service If the Condair RS must be replaced or if the Condair RS is not needed any more, proceed as follows: 1. Take the Condair RS out of operation as described in chapter 4.5.
±1 % absolute humidity (with PI-control and use of de-ionized water) Note: When operating the Condair RS with option P with potable water the control ac- curacy can deviate from the above stated values during the drain cycle. For process air humidification with constant control accuracy the Condair RS with option P must be operated with de-ionized water and the drain cycle can be reduced.