Figure 97 provides an example of a Type Code 2 ePDU alarm number code.
Number code 211402: Eaton ePDU Critical Overcurrent L2 Phase
2 1 1 4 0 2
Type code 2 = Eaton ePDU
Figure 97. Example Type 2 Code
Table 11 lists ePDUand User alarms and events.
Table 11. ePDU and User Alarms and Events
Identification and
Type Code
Index Code
2
201000
2
201100
2
202000
2
202100
2
203000
2
203100
2
204000
2
204100
2
205000
2
205100
2
208000
2
208100
2
206000
2
206100
2
206200
2
206300
2
206400
2
207000
2
207100
2
207200
2
207300
Identi cation code = 114
Alarm or Event
Dry Contact 1 Not Active
Dry Contact 1 Active
Dry Contact 1 Open
Dry Contact 1 Closed
Dry Contact 2 Not Active
Dry Contact 2 Active
Dry Contact 2 Open
Dry Contact 2 Closed
Sensor Probe Communication Failure Cleared
Sensor Probe Communication Failure
Sensor Probe Not Connected
Sensor Probe Connected
Humidity No Threshold
Humidity Warning Low Threshold
Humidity Critical Low Threshold
Humidity Warning High Threshold
Humidity Critical High Threshold
Temperature No Threshold
Temperature Warning Low Threshold
Temperature Critical Low Threshold
Temperature Warning High Threshold
Eaton ePDU G3 Operation Manual P-164000277—Rev 5
Maintenance and Alarms
Index code = 02
Description
The signal for Dry Contact 1 is active.
The signal for Dry Contact 1 is not active.
Dry Contact 1 is open.
Dry Contact 1 is closed.
The signal for Dry Contact 2 is active.
The signal for Dry Contact 2 is not active.
Dry Contact 2 is open.
Dry Contact 2 is closed.
Sensor Probe communication failure is cleared
Sensor probe communication failure detected
Sensor probe not connected since firmware startup
Sensor probe connected at least once since firmware
startup
No humidity threshold has been triggered.
The humidity level reading is less than the value
configured as the low humidity warning threshold.
The humidity level reading is less than the value
configured as the low humidity critical threshold.
The humidity level reading is greater than the value
configured as the high humidity warning threshold.
The humidity level reading is greater than the value
configured as the high humidity critical threshold.
No temperature threshold has been triggered.
The temperature level reading is less than the value
configured as the low temperature warning
threshold.
The temperature level reading is less than the value
configured as the low temperature critical threshold.
The temperature level reading is greater than the
value configured as the high temperature warning
threshold.
130