1MRS 751802-MUM
10.
10.1.
10.1.1.
Protection Relay
Technical Reference Manual, Standard Configurations
Application examples, Medium
Outgoing feeder, Medium M01
Features
This application example describes an outgoing feeder of a single busbar including:
• overcurrent protection
• directional earth-fault protection
• phase discontinuity protection
• thermal overload protection for cable/line
The network is compensated earthed or isolated. Three-phase current measurement
is established with a set of current transformers and the neutral current is measured
with a cable transformer. The residual voltage is measured with a set of voltage
transformers in an open-delta connection.
)LJ 5(; 0 XVHG IRU SURWHFWLRQ PHDVXULQJ DQG VXSHUYLVLRQ RQ
DQ RXWJRLQJ IHHGHU LQ D VLQJOH EXVEDU V\VWHP 7KH V\VWHP HDUWKLQJ
RI WKH VXSSO\LQJ QHWZRUN LV HLWKHU FRPSHQVDWHG RU LVRODWHG
MCS
3I >
50/51
TCS
I >
67N
0
CBCM
I >
46
3I~harm
3
49F
CBFP
62
3I
U
0
Application Example 5
REX 521 M01
REX 521
000
0
I
R
I
0
143