Input Switchgroups (Swgrp) - ABB REX 521 Technical Reference Manual, Standard Configurations

Protection relay
Table of Contents

Advertisement

1MRS 751802-MUM
4.1.2.
Protection Relay
Technical Reference Manual, Standard Configurations
Selector
DI1
.
.
.
DI9
)LJ 
8VH RI LQSXW VHOHFWRUV

Input switchgroups (SWGRP)

Switchgroups are used for connecting input signals to the inputs of the function
blocks. Switchgroups allow the connection of one input signal to several function
block inputs. Refer to Fig. 4.1.3.-1 for all the signals available for each input
switchgroup. The settings can be found in Main
menu\Configuration\Input SWGRP.
SWGRP
Reset 1
)LJ 
7KH LQSXW VLJQDO LV URXWHG ZLWK WKH VZLWFKJURXS WR RQH RU VHYHUDO
IXQFWLRQ EORFN LQSXW V
Note that the symbol O/C (overcurrent) includes overcurrent function blocks I>, I>>
and I>>>. The E/F (earth-fault) symbol includes all three earth-fault function blocks
Io>, Io>> and Io>>>, e.g. the Reset 1 signal resets all the three stages.
The symbols O/C and E/F are used in the overview diagrams of the signal routings
and in the HMI menus.
Reset 1
Selector
Reset 2
Selector
Blocking 1
Selector
Selector
Blocking 2
Selector
etc.
RESET OC
RESET EF
RESET Iub
etc.
REX 521
55