Implementations; 1.Definite Trip Alarm To Output Relay - ABB REX 521 Technical Reference Manual, Standard Configurations

Protection relay
Table of Contents

Advertisement

REX 521
10.3.6.
10.3.6.1.
164
Protection Relay
Technical Reference Manual, Standard Configurations
REX 521
)LJ  &RQQHFWLRQ GLDJUDP IRU WKH VWDQGDUG FRQILJXUDWLRQ 0 ZLWK
EUHDNHU VWDWXV LQGLFDWLRQ DQG FRQWURO VLJQDOV IRU RSHQLQJ DQG
FORVLQJ RI WKH FLUFXLW EUHDNHU

Implementations

In the sections below a few implementation examples for the standard configuration
M02 are presented.
Definite trip alarm to output relay
To receive the DEFTRIP signal on an output contact go to
Main menu\Configuration\Output SWGRP\0->1 Alarm 1, press the
[E]-button and scroll to the DEFTRIP and take it in to use with the help of the [
[↓]
and
push buttons. The checksum for 0->1 Alarm 1 is then 32. The 0->1 Alarm1
signal can then be routed to an output contact, in this example SO2, in
Main menu\Configuration\Output signals\.
CB
1MRS 751802-MUM
0
1
CLOSE circuit breaker
TRIP circuit breaker
↑]