Table 2.-2 Protection functions available in the different standard
configurations of the REX 521
Function
Description
3I>
Three-phase non-directional overcurrent protection, low-set stage
3I>>
Three-phase non-directional overcurrent protection, high-set stage
3I>>>
Three-phase non-directional overcurrent protection, instantaneous stage
Io>
Non-directional earth-fault protection, low-set stage
Io>>
Non-directional earth-fault protection, high-set stage
Io>>>
Non-directional earth-fault protection, instantaneous stage
Io>->
Directional earth-fault protection, low-set stage
Io>>->
Directional earth-fault protection, high-set stage
Io>>>->
Directional earth-fault protection, instantaneous stage
3I>->
Three-phase directional overcurrent protection, low-set stage
3I>>->
Three-phase directional overcurrent protection, high-set stage
3U>
Three-phase overvoltage protection, low-set stage
3U>>
Three-phase overvoltage protection, high-set stage
3U<
Three-phase undervoltage protection, low-set stage
3U<<
Three-phase undervoltage protection, high-set stage
3I2f>
Three-phase transformer inrush and motor start-up current detector
Iub>
Phase discontinuity protection
3Ith>
Three-phase thermal protection for cables
O->I
Auto-reclose function (5 shots)
Uo>
Residual overvoltage protection, low-set stage
Uo>>
Residual overvoltage protection, high-set stage
Uo>>>
Residual overvoltage protection, instantaneous stage
f1
Underfrequency or overfrequency protection, stage 1
f2
Underfrequency or overfrequency protection, stage 2
SYNC
Synchro-check / voltage-check function
Table 2.-3 Control functions available in the different standard configurations
of the REX 521
Function
Description
I<->O CB1
Circuit breaker control with indication
I<->O IND1
Object indication
I<->O IND2
Object indication
I<->O POS
Logic control position selector
Table 2.-4 Measurement functions available in the different standard
configurations of the REX 521
Function
Description
3I
Three-phase current measurement
Io
Neutral current measurement
Uo
Residual voltage measurement
DREC
Transient disturbance recorder
3U
Three-phase voltage measurement