Outgoing feeder, High H04
Features
This application example describes an outgoing feeder of a single busbar including:
• auto-reclosure function
• overcurrent protection
• directional and non-directional earth-fault protection
• phase discontinuity protection
• thermal overload protection for cable or line
This application example is an optional solution for the seventh application example
(chapter 8.7), if extended earth-fault protection against a cross-country fault is
required or wider range of measurements is needed.
The network is either compensated or isolated. Three-phase current measurement is
established with a set of current transformers. The neutral current I
with a cable current transformer and the neutral current I
connection of the phase current transformers. The residual voltage is measured with
a set of voltage transformers in an open-delta connection. Phase-to-phase voltage
measurements are established with voltage transformers.