Protection Relay
Technical Reference Manual, Standard Configurations
Note: In sensor standard configurations (H01S and H03S) the parameter Control
settings\Voltage combine must be enabled and in transformer standard
configuration (H03) it must be disabled. The parameter is by default in the correct
mode.
SYNC
Command SC_OK
)LJ  )XQFWLRQ EORFN V\PERO RI 6<1&
Synchro-check, SYNC1
Umax
Umin
dU
dphase
df
Energizing mode
Operation mode
Synchro mode
Operate time
Check time
Operation accuracy
Reset time
Reset ratio typically
Operate time accuracy

Control

I<->O CB1
The circuit-breaker function block is used for controlling the open and close
positions of a circuit breaker. The function block also takes care of the user-defined
interlocking logics and has guaranteed opening and closing pulse widths and forced
open control operations for protection purposes. The open, close and undefined
states of an object can be indicated remotely by the function block. Since the
function block is mainly designed for circuit breakers, it will issue specific alarm
signals based on the condition monitoring features.
0.50...1.00 x Un
0.10...0.80 x Un
0.02...0.60 x Un
5...90°
0.02...5.00 Hz
Not in use
U1->U2, U2->U1
U1->U2
U2->U1
U1>U2,U2>U1,0>0
Command mode
Continuous mode]
Not in use
Asynchr. Mode
Synchr. Mode
0.10...20.0 s
0.05...300.0 s
Note! The values below apply when f/fn = 0.95...1.05
Voltage measurement: ±2.5% of set value or ± 0.01 x Un
Frequency measurement: ±10 mHz
Phase angle measurement: ±2°2
< 50 ms
0.975 x Un
±2% of set value or ±20 ms