Specifications
Battery Requirements
Group 27F, 12 Volt
NOTE: Battery dimensions (L x W x H) for Group 27F battery must not exceed 12-1/2" x 6-13/16" x 8-15/16"
(318 mm x 173 mm x 227 mm).
Group 31, 12 Volt
NOTE: Battery dimensions (L x W x H) for Group 31 battery must not exceed 13" x 6-13/16" x 9-7/16"
(330 mm x 173 mm x 240 mm).
Battery Charger
The battery charger is integrated into the control panel
module. It operates as a "Smart Charger" which ensures
output charging levels are safe and continuously
optimized to promote maximum battery life.
Battery Disposal
WARNING
Environmental Hazard. Always recycle batteries at an
official recycling center in accordance with all local
laws and regulations. Failure to do so could result in
environmental damage, death or serious injury.
Accessories
See
Figure
2-3. The following product accessories are available. Contact an IASD for additional information
1. Scheduled Maintenance Kit (Part No. G007640-0; 15/20 kW)
2. Scheduled Maintenance Kit (Part No. G007641-0; 30 kW)
3. Cold Weather Kit (Part No. G007650-0: 15/20 kW;
Part No. G007651-0: 30 kW)
4. Vent Extension Support Kit (Part No. G006588-1)
5. Fuel Fill Drop Tube (Part No.G006507-0)
6. Lockable Fuel Fill Cap (Part No. G006512-0)
7. Emergency Stop Switch (Part No. G006510-0)
8
2.5L & 2.2L engine: For areas where temperatures regularly drop below 32° F (0° C).
Upgrade option for 2.2L engine: For areas where temperatures regularly drop below
32° F (0° C).
(000228)
Always recycle batteries in accordance with local laws
and regulations. Contact your local solid waste collection
site or recycling facility to obtain information on local
recycling processes. For more information on battery
recycling, visit the Battery Council International website
at: http://batterycouncil.org.
Corrosion Protection
Periodically wash and wax the enclosure using
automotive
type
products.
recommended in salt water/coastal areas.
8. Touch-Up Paint Kit (Part No. G005703-0)
9. Five Gallon Spill Box (Part No. G006502-0)
10. Fuel Tank Risers (Part No. G006505-0: 15/20 kW;
Part No. G006506-0: 30 kW)
11. 90% Fuel Fill Level Alarm (Part No. G006504-0)
12. Spill Box Drain Back (Part No. G006511-0)
13. Stainless Steel Fuel Lines
(Part No. G007660-0 (15/20 kW); G007661-0 (30 kW))
14. Mobile Link™ (Part No. G006463-4) (not pictured)
Owner's Manual for Stationary Diesel Generators
Frequent
washing
is
.
Need help?
Do you have a question about the Protector Series and is the answer not in the manual?