Protection Systems; Emissions; Fuel Requirements; Battery Requirements - Generac Power Systems PWRgenerator 9 kW Owner's Manual

Air-cooled generator
Hide thumbs Also See for PWRgenerator 9 kW:
Table of Contents

Advertisement

General Information

Protection Systems

The generator may need to run for long periods of time
with no operator present to monitor engine or generator
conditions. The generator is equipped with protection
systems to automatically shut down the unit to protect
against potentially damaging conditions. Some of these
systems include:
Alarms:
High Temperature
Low Oil Pressure
Overcrank
Overspeed
Overvoltage
Undervoltage
Overload
Warnings:
Charger Warning
Low Battery
Battery Problem
The control panel contains a display alerting the operator
when a fault condition occurs. The above list is not all-
inclusive. See
Operation
alarms and control panel operation.
NOTE: A warning indicates a condition on the generator
which should be addressed, but will not shut down gener-
ator. An alarm shuts down the generator to protect sys-
tem from any damage. In event of an alarm, an owner
can clear the alarm and restart generator prior to contact-
ing an IASD. Contact an IASD if the intermittent issue
occurs again.

Emissions

The United States Environmental Protection Agency (US
EPA) (and California Air Resources Board (CARB), for
engines/equipment certified to California standards)
requires this engine/equipment to comply with exhaust
and evaporative emissions standards. Locate the emis-
sions compliance decal on the engine to determine appli-
cable standards. See the included emissions warranty for
emissions warranty information. Follow the maintenance
specifications in this manual to ensure the engine com-
plies with applicable emissions standards for the duration
of the product's life.
This generator is certified to operate on liquid propane
vapor fuel or pipeline natural gas.
The Emission Control System code is EM (Engine Modifi-
cation). The Emission Control System on this generator
consists of the following:
10
Underspeed
RPM Sensor Loss
Controller Fault
Wiring Error
Stepper Overcurrent
Exercise Set Error
USB Warning
Download Failure
for more information about
:
System
Components
Air Induction
- Intake manifold
- Air cleaner
Fuel Metering
- Electronically controlled mixer
assembly
Ignition
- Spark plug
- Ignition module
Exhaust
- Exhaust manifold
- Muffler

Fuel Requirements

DANGER
Explosion and Fire. Fuel and vapors are extremely
flammable and explosive. Add fuel in a well
ventilated area. Keep fire and spark away. Failure
to do so will result in death or serious injury.
The engine has been fitted with a dual fuel electronic fuel
injection control (EFIC) system. The unit will run on NG
or LP gas, but has been factory-configured to run on NG.
The fuel system will be configured for the available fuel
source during installation.
Recommended fuels should have a BTU content of at
3
least 1,000 BTUs per ft
natural gas, or at least 2,500 BTUs per ft
3
joules per m
) for LP gas.
NOTE: If converting to LP gas from NG, a minimum LP
tank size of 250 gal (946 L) is recommended. See instal-
lation manual for complete procedures and details.

Battery Requirements

12 volts, Group 26R Wet Cell 540CCA minimum (not
included with unit). See
Battery Maintenance
battery maintenance procedures.

Battery Charger

The battery charger is integrated into the converter mod-
ule in all models. It operates as a smart charger, verifying
output charging levels are safe and continuously opti-
mized to promote maximum battery life.
NOTE: Do not use external battery chargers.

Engine Oil Requirements

See
Engine Oil Requirements
Owner's Manual for PWRgenerator Air-Cooled Generators
(000105)
(37.26 megajoules per m
3
(93.15 mega-
for correct
for correct oil viscosity.
3
) for