30 Hour Break-In
Perform the following task:
•
Replace Lubricating Oil and Oil Filter
NOTE: See
Replace Lubricating Oil and Oil Filter
under Schedule B Maintenance.
Daily Maintenance (If Running
Continuously)
Perform the following tasks:
•
Check Fuel Level and Fill
•
Drain Fuel Filter
•
Check Fuel Lines and Hoses
•
Check Coolant Level
•
Check Coolant Hoses
•
Check Radiator for Clogging
•
Check Lubricating Oil Level
NOTE: See
Preliminary Instructions
Lubricating Oil Level
under Schedule A Maintenance.
Schedule A Maintenance
NOTE: Perform Schedule A maintenance once each
year or after 125 hours of service, whichever comes first.
Preliminary Instructions
1. See
Remove From
2. Remove access panels at the front and both sides
of the enclosure. See
Owner's Manual for Stationary Diesel Generators
PUSH TO TRIP
Figure 5-6. Generator Control Panel
through
Service.
Access
Panels.
3. Remove negative battery cable (black) from
negative (-) battery terminal.
NOTE: For general location of components, see
Component
Locations.
Check Fuel Level and Fill
1. Observe fuel gauge to note level of fuel in tank.
See
Figure
2. Remove fuel fill cap from filler pipe.
3. Add fuel until needle on fuel gauge approaches the
F(ull) mark.
4. Install fuel fill cap onto filler pipe.
Check
Figure 5-7. Check Fuel Level Gauge and Fill
C
B
5-7.
Maintenance
006374
006381
31