CMM365A-2G CLOUD MONITORING COMMUNICATION MODULE USER MANUAL SMARTGEN (ZHENGZHOU) TECHNOLOGY CO., LTD.
Page 2
SmartGen Technology at the address above. Any reference to trademarked product names used within this publication is owned by their respective companies. SmartGen Technology reserves the right to change the contents of this document without prior notice. Table 1 - Software Version Date...
APP (IOS or Android) and PC terminal devices. CMM365A-2G module not only can achieve genset monitoring but also can insert some digital alarm input/output signal to achieve monitoring of generator room entrance guard, guard against theft and fire facilities.
CMM365A-2G Cloud Monitoring Communication Module User Manual SPECIFICATION Table 2 – Technical Data Items Contents Operating Voltage DC 8.0V~35.0V, continuous power supply Standby: ≤2W Power Consumption Working: ≤5W Digital Input Volt free digital Input Relay Output 1A DC30V Volts free output...
RS485 MASTER(Red) Normally Light: Communication fail; Blink: Communication normal. Normally Extinguish: not communication; RS485 SLAVE(Red) Blink: Communication normal. Extinguish: CMM365A-2G fail to login on the server; GPRS(Red) Light: Registered successfully; Blink: Real data communication normal. Normally Extinguish: Disabled; LINK(Red) Normally Light: Communication fail;...
Connect GPRS antenna to CMM365-2G antenna port. Fig.2 – GPRS Antenna Connection Schematic Diagram MASTER RS485 Connect master RS485 interface to CMM365A-2G. RS485 interface to achieve genset data information. If communication is abnormal, 120Ω terminal resistance is recommonded. One end of shield wire hangs in the air and the other one connects with SCR.
Receive genset data information by connecting module LINK port with Genset Controller LINK port. Fig. 5 – LINK Connection Schematic Diagram USB DEVICE Configure all the parameters and view CMM365A-2G ID&Login password by connecting USB port with USB disk of PC software. Fig.6 – USB Connect PC Device...
CMM365A-2G Cloud Monitoring Communication Module User Manual TERMINAL Table 4 – Terminals Description Function Cable Size Note 1.0mm Connected with negative of starter battery. Connected with positive of starter battery. 3A fuse 1.0mm is recommended. Digital. Input 1 1.0mm Active when connect to B-.
CMM365A-2G Cloud Monitoring Communication Module User Manual PROGRAMMABLE PARAMETERS CONTENTS AND SCOPES OF PARAMETERS Table 5 – Parameter Content & Scope Item Range Default Description Gateway Site Name (0-65535) 20 Chinese characters/letters/digits Server URL (0-65535) www.monitoryun.com 40 characters Server Port...
20s. Reserved Reserved Reserved Reserved Reserved Reserved PC CONFIGURATION INTERFACE Connecting the USB port of CMM365A-2G communication module with PC USB port to configure the parameters. CMM365-2G Cloud Monitoring Communication Module 2017-12-25 Version 1.0 Page 11 of 15...
Page 12
CMM365A-2G Cloud Monitoring Communication Module User Manual Fig. 7 - Gateway Configuration Figure 8 - Module Monitoring Interface CMM365-2G Cloud Monitoring Communication Module 2017-12-25 Version 1.0 Page 12 of 15...
CMM365A-2G Cloud Monitoring Communication Module User Manual SYSTEM DIAGRAM One CMM365A-2G module connects with one genset monitor module. It can be connected via RS485 port and LINK port. Fig.9 - CMM365A-2G System Diagram CMM365-2G Cloud Monitoring Communication Module 2017-12-25 Version 1.0...
CMM365A-2G Cloud Monitoring Communication Module User Manual CASE DIMENSION AND INSTALLATION 2 ways for installation: 35mm guide rail in box or screw (M4) installation as below: Fig.10 - CMM365A-2G Case Dimension Fig.11 - CMM365A-2G Guide Rail Installation Fig.12 - CMM365A-2G Screw Installation...
CMM365A-2G Cloud Monitoring Communication Module User Manual TROUBLESHOOTING Table 8 – Fault Finding Symptoms Possible Solutions Controller no response with Check power voltage; power. Check controller connection wirings. Check SIM card is inserted or not; GPRS Indicator Not Light Check GPRS antenna is connected or not.