Danfoss MCB 152 Operating Instructions Manual page 43

For vlt automationdrive fc 302
Hide thumbs Also See for MCB 152:
Table of Contents

Advertisement

Maintenance, Diagnostics an...
LCP Message
Status
!1(1)
0 RPM
0.00 A
0.00KW
SO General Reset
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Req. RESET
Status
!1(1)
0 RPM
0.00 A
0.00KW
SO Ext.Fail: XXX_STO
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Req. RESET
Status
!1(1)
0 RPM
0.00 A
0.00KW
SO Int.Fail: XXX_STO
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Trip Lock
MG37F102
Operating Instructions
Description
The LCP shows this message
after resetting the safety
option with MCT 10 Set-up
Software. After the reset, the
safety option is set to blank
initial state. For more
information, see
chapter 6.1.3 Password
Protection.
The LCP shows this message
when the safety option
detects an external error. The
LCP shows the error number.
For information about the
errors and possible solutions,
see chapter 9.3.1 List of Error
Conditions. To resume normal
operation, ensure that the
source of the error has
ceased and reset the safety
option.
The LCP shows this message
when the safety option
detects an internal error. The
LCP shows the error number.
For information about the
errors and possible solutions,
see chapter 9.3.1 List of Error
Conditions. To resume normal
operation, ensure that the
source of the error has
ceased and power cycle the
safety option.
Danfoss A/S © 10/2014 All rights reserved.
LCP Message
Status
!1(1)
750 RPM
0.00 A
0.00KW
25 Hz
50 %
!Safe Option Failure [W252]
Auto Remote Run on ref.
Table 9.2 LCP Messages
LCP Message
Status
!1(1)
0 RPM
0.00 A
0.00KW
SO Custom. completed
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Req. RESET
Status
!1(1)
0 RPM
0.00 A
0.00KW
SO Custom. aborted
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Req. RESET
Status
!1(1)
0 RPM
0.00 A
0.00KW
Safe Opt. initialized
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Req. RESET
Table 9.3 LCP Messages, Safe Fieldbus Disabled
Description
The LCP shows this message
when the safety option
detects an issue and cannot
handle the issue as an
internal or external error. A
manual user action is
required in this situation. This
situation can occur in the
following cases:
PUST timer expired. To
resume normal operation,
power cycle the safety
option.
DI1 offline timer expired.
Test DI1 by activating it.
DI2 offline timer expired.
Test DI2 by activating it.
To configure the LCP to show
a dedicated message for each
warning, select 42-86 Safe
Option Info in 0-23 Display
Line 2 Large or in 0-24 Display
Line 3 Large.
Description
The safety option customi-
sation with MCT 10 Set-up
Software is completed. Reset
the safety option to start the
normal operation.
The safety option customi-
sation with MCT 10 Set-up
Software was aborted. The
safety option uses the
previous configuration. Reset
the safety option to start the
normal operation.
The safety option was
powered up. After the Power
up Self Test (PUST), the safety
option requests a reset.