Lcp Messages; Lcp Status Messages - Danfoss MCB 152 Operating Instructions Manual

For vlt automationdrive fc 302
Hide thumbs Also See for MCB 152:
Table of Contents

Advertisement

Maintenance, Diagnostics an...
Error
No.
Description
119
External error:
Safe fieldbus
destination
address
mismatch.
Reaction: STO.
120
External error:
Safe fieldbus
telegram
mismatch.
Reaction: STO.
121
External error:
PROFIsafe
configuration
error. Reaction:
STO.

9.4 LCP Messages

Any errors on the safety option are indicated on the
frequency converter.
9
9
The following options are available for detailed diagnostics
and error detection:
LEDs on the front of the safety option provide
information on operating states. The LEDs are
used to indicate the status of the option, i.e.
active safety functions, failures and warnings, if
any.
LCP text or info via bus display the status of the
safety functions (for example STO).
The following messages are displayed in online mode in
the MCT 10 Set-up Software:
Status of the safety option.
Internal and external errors and the
corresponding troubleshooting tips.
To configure the LCP to show the safety option specific
information, use the parameters in parameter group 0-2*
LCP Display.
0-20 Display Line 1.1 Small, 0-21 Display Line 1.2 Small, and
0-22 Display Line 1.3 Small have the following options:
42-82 Safe Control Word.
42-83 Safe Status Word.
42-85 Active Safe Func.
0-23 Display Line 2 Large, 0-24 Display Line 3 Large have the
following options:
40
Safety Option MCB 152
Reason
Destination address on
Make sure that the addresses
the safe fieldbus is
of the PLC and the safety
invalid.
option match.
Safe fieldbus telegram
Check the telegram format
is invalid.
settings in the safe PLC and
the safety option.
PROFIsafe configuration
Check the settings of the
is invalid.
safety option and the PLC.
Danfoss A/S © 10/2014 All rights reserved.
Led Indications
Action
LED1
Status of LED 1 and LED2
depends on safety function
state assigned to DI1 and
DI2.
42-82 Safe Control Word.
42-83 Safe Status Word.
42-86 Safe Option Info.

9.4.1 LCP Status Messages

This section describes the LCP status messages related to
the safety option. The set of messages is different
depending on whether or not a safe fieldbus is enabled.
Table 9.2 contains messages that are shown regardless of
the safe fieldbus state. Table 9.3 contains messages that
are shown only when the safe fieldbus is disabled.
LCP Message
Status
0 RPM
0.00 A
0.0 Hz
50.0 %
!Safe Stop [W68]
Auto Remote Coast
Status
0 RPM
0.00 A
Safe Func. Pending
SO RESET required!
!Safe Stop [W68]
Auto Remote SO Req. RESET
LED2
LED3
Red flashing
Red flashing
(500 ms on/
(500 ms on/
off).
off).
Red flashing
Red flashing
(500 ms on/
(500 ms on/
off).
off).
Red flashing
Red flashing
(500 ms on/
(500 ms on/
off).
off).
Description
The safety function was
!1(1)
activated via a digital input or
0.00KW
PROFIsafe.
The source that triggered the
!1(1)
safety condition has ceased,
0.00KW
but the safety option is
waiting for the reset signal to
continue normal operation.
The LCP shows this message
only if the manual restart
behaviour is selected for the
digital input.
The LCP does not show this
message when the PROFIsafe
control word activates the
safety function, since the
PROFIsafe configuration uses
automatic restart behaviour.
LED4
MG37F102

Advertisement

Table of Contents
loading

This manual is also suitable for: