description of 0-68 Safety Parameters Password
and 0-69 Password Protection of Safety Parameters
in chapter 7 Parameter Set-up.
3.
The LCP shows the SO Data Confirmation
message.
4.
Press OK to overwrite the safety parameters in
the safety option.
5.
Depending on the actual safety parameter config-
uration, a reset signal to the safety option can be
required. For information about the reset
functionality, see chapter 6.3 Reset Function.
6.
Perform the commissioning test to ensure that
the correct safety parameter configuration is
transferred to the safety option. See
chapter 5.4 Commissioning Test. Use the commis-
sioning test report for the safety parameter
configuration that is being transferred.
If replacing the frequency converter, use the same
functionality and select SO in step 1 instead of VLT.
9.2.4 Copying Safe Parameter
Configuration
The frequency converter allows to copy safety parameters
using the LCP. This functionality allows to set-up a
different frequency converter with exactly the same safety
parameter configuration without using the MCT 10 Set-up
Software.
Follow the steps below, to copy a pre-defined safety
parameter configuration from 1 frequency converter to
another:
1.
Select [1] All to LCP in 0-50 LCP Copy. Monitor the
upload process on the progress bar.
2.
Install the LCP with all the copied parameters on
the frequency converter that needs to be
updated.
3.
Select 1 of the following options:
[2] All from LCP in 0-50 LCP Copy, to
copy all frequency converter parameters
including the safety parameters.
[9] Safety Par. from LCP in 0-50 LCP Copy,
to copy only the safety parameter
configuration.
4.
Continue with steps 2–6 in chapter 9.2.3 Mismatch
of Safety Option Parameters to finish the safety
parameter copy process.
For the example of a commissioning set-up with LCP
copying, see chapter 5.6 Commissioning Set-up Examples.
MG37F102
Operating Instructions
Danfoss A/S © 10/2014 All rights reserved.
9
9
35