Commissioning
5.
Make other application specific settings.
6.
In the Safe plug-in, click Write to Drive.
7.
If the safety option is in blank initial state, it
prompts the user to change the password.
7a
In the New password dialog box, enter
the current password (which is the
default password - 12345678) and the
new password and click OK.
7b
The Safe plug-in shows the confirmation
message. Click OK.
8.
In the Confirm password dialog box, enter the
new safety option password and click OK.
9.
In the Configuration Approval dialog box, verify
the safety configuration and click Approve to start
writing the safety parameters.
MG37F102
Operating Instructions
10.
11.
12.
13.
14.
Danfoss A/S © 10/2014 All rights reserved.
Click Cancel to abort the customisation process
and revert the previous safety option state.
The MCT 10 Set-up Software opens the Writing
Safety Parameters dialog box.
When the progress bar reaches 100%, the safety
parameters are written.
The MCT 10 Set-up Software generates and opens
the commissioning report.
Save and print the commissioning report. The
report is required for future maintenance.
Close the commissioning report dialogue box and
the Writing Safety Parameters dialog box.
The safety option customisation is now complete.
A reset may be required depending on the safety
option configuration. Up to 10 may elapse before
the safety option is ready for operation.