Reset Function; Reset Input (Di2) - Danfoss MCB 152 Operating Instructions Manual

For vlt automationdrive fc 302
Hide thumbs Also See for MCB 152:
Table of Contents

Advertisement

Configuring the Safety Opti...
Bit 11 = 1, An internal error is active.
Bit 12, Reset
Bit 12 = 0, No safety option reset is required.
Bit 12 = 1, A safety option reset is required .
Bit 13, Pending fail safe state
Bit 13 = 0, No pending fail safe state.
Bit 13 = 1, The safety option is in this state at each power-
up.
Bit 14, External error
Bit 14 = 0, No external error is active.
Bit 14 = 1, external error is active.
Bit 15, Safe function pending
Bit 15 = 0, No safe function is pending.
6
6
Bit 15 = 1, A safe function is pending.
Bit 16, General reset
Bit 16 = 0, No change in state
Bit 16 = 1, A general reset is done.
Bit 17, Customisation confirmed
Bit 17 = 0, No change in state.
Bit 17 = 1, Customisation confirmed by user.
Bit 18, Customisation aborted
Bit 18 = 0, No change in state.
Bit 18 = 1, Customisation aborted by user.
Bit 19, Customisation requested
Bit 19 = 0, No change in state.
Bit 19 = 1, Customisation is requested by user.
Bit 20, Suspension of speed monitoring
Bit 20 = 0, No change in state.
Bit 20 = 1, Suspension of speed monitoring – see error
code.
Bit 21, Power up self test warning
Bit 21 = 0, No change in state
Bit 21 = 1, A power up self test warning is issued.
Bit 22, Digital input 1 offline test warning
Bit 22 = 0, No change in state.
Bit 22 = 1, Digital input 1 offline test warning
Bit 23, Digital input 2 offline test warning
Bit 23 = 0, No change in state.
Bit 23 = 1, Digital input 2 offline test warning.
Bit 24-31
These bit indicate a reason for internal or external errors,
for more information, see the error codes.
42-81 Safe Option Status 2 indicates which digital input of
the safety option is activated, in pending state or in blank
initial state.
22
Safety Option MCB 152
Bit
0
1
2
3
4
5
6
7
8
9-31
Table 6.4 Status Bits for Safety Option Status 2

6.3 Reset Function

When the safety function is activated, reset the safety
option. Depending on the configuration, the following
sources can reset the safety option:
Parameter 42-24 Restart Behaviour determines whether the
safety option restarts automatically, or waits for a manual
reset after the safety function was activated:
For more information, read the description of 42-31 Reset
Source and its options in chapter 7.1 Parameter List.

6.3.1 Reset Input (DI2)

If manual reset is configured, wire the DI2A reset input
terminal to a 24 V DC via an NO switch. The manual reset
can also be used to reset external errors detected by the
safety option.
Danfoss A/S © 10/2014 All rights reserved.
Description
00 - Inactive
DI1 safety status
01 - Active
10 - Pending
00 - Inactive
DI2 safety status
01 - Active
10 - Pending
Blank initial state
0 (inactive)/1 (active)
000 - No safe fieldbus
supported
Safe fieldbus support
001 - PROFIsafe
supported.
Safe function status on
0 - Deactivated
safe fieldbus
1 - Activated
Not used
-
The Reset key on the LCP or the frequency
converter's digital input.
The digital input on the safety option (DI2_A).
The reset signal via the safe fieldbus.
The automatic reset function.
Manual reset behaviour - when the safety
function is activated, the safety option requires a
reset from a reset source before it can run again.
Automatic reset behaviour - when the safety
function is activated, the safety option can run
again as soon as the condition that triggered the
safety function ceases. This behaviour is only
valid for the digital input where this reset
behaviour is defined. For instance, in case of an
external error, a manual reset from the reset
source is required regardless of the setting in
42-24 Restart Behaviour.
State
MG37F102