Mounting The Poolstat Control With Front-Mounted Loop Using Mounting Slots - Raypak raytherm p-1826 Installation & Operating Instructions Manual

Commercial swimming pool heater
Table of Contents

Advertisement

Fig. 11: Companion Flange Connections
(Models 926/962–1287/1336 with H-Bypass)
3" Outlet
2" Slip
Ball Valve
Inlet/Outlet
Header
Fig. 12: Companion Flange Connections
(Models 2100–4001)
Connection
Model No.
Size
926–1223
2" FPT
with UG
1287–1826
2-1/2" FPT
2100–4001
3" FPT
Table C: Water Connections
Loop* Flow Rates
Model No.
(gpm)
1287/1336
30–50
1414/1468
35–55
1571/1631
40–65
1758/1826
45–70
2100
50–80
2500
60–95
3001
75–115
3500
90–135
4001
100–150
*Loop is secondary piping to heater from main system.
Table D: Flow Rates
3" Inlet
2 H.P. Pump
Minimum
Maximum
gpm
gpm
60
100
Refer to Table D
Heater Flow
Rates (gpm)
85
85
85
85
180
180
180
180
180
Raypak recommends the installation of an air bleed
vent at a suitable location (usually the highest point in
the plumbing) to remove air from the piping system.
These units should be available at your local whole-
sale supplier. Raypak does not provide this item.
CAUTION: Power to the heater should be
interlocked with the main system pump to make
sure the heater does not fire without the main
system pump in operation. Improper flow control can
damage the heater. Uncontrolled flow (too high) or
restricted flow (too low) can seriously affect heater
operation. Follow these instructions to make sure
your heater is properly installed.
Models with H-bypass are equipped with an external
pump and bypass arrangement that blends outlet
water with the inlet to increase the inlet water tempera-
ture, thereby reducing the likelihood of condensation
forming on the heat exchanger. The pump also serves
to circulate water through the heater from the main
system piping. Adjust the bypass to maintain 105ºF
inlet.
To complete the installation of the pool heater, the
poolstat needs to be installed in the main return water
line. This will ensure that the heater will be energized
at the right time. If the main water line is too far away
from the heater and the capillary bulb will not reach it,
locate the poolstat adjacent to the main line and run
wires back to the heater. Follow the instructions listed
below to install the poolstat.
Mounting the Poolstat Control
with Front-Mounted Loop
Using Mounting Slots
For heater models:
1287, 1336, 1414, 1468, 1571, 1631, 1758, 1826,
2100, 2500, 3001, 3500, 4001.
NOTE: For more detail on piping, refer to the
diagrams on pages 15, 16 & 17.
1. Remove the poolstat control cover by removing
the two cover screws at the top. See Fig. 13 & 14.
12