Clearances; Combustion Air (Indoor Units Only) - Raypak raytherm p-1826 Installation & Operating Instructions Manual

Commercial swimming pool heater
Table of Contents

Advertisement

Clearances

All Heaters
For clearances from combustible surfaces, see
Table A below. A minimal vertical clearance of three
feet between the upper surface of the flue outlet to a
noncombustible material is required.
Indoor Heaters
Heater
Clearance
Side
(Inches)
Top
24
Back
24
Right Side
24
Left Side
24
Vent*
6
*Vent includes factory supplied drafthood and does not include field
supplied vent systems above the drafthood. On Models 2100-4001
drafthood is built into heater.
For servicing provide a front clearance as shown below:
Model 926/962-758/1826 - 24"
Model 2100-4001 - 48"
Table A: Minimum Clearances from Combustible
Construction
For servicing, provide at least 24" in front of the heater
on Models 926-1826 & 48" in front of the heater on
Models 2100-4001 for burner tray removal, and at
least 18" on the right side of the heater to inspect and
delime the heat exchanger.
Outdoor Heaters (Models 926-1758)
These heaters are design-certified for outdoor installa-
tion, when equipped with the approved top designated
for outdoor use. Heaters must not be installed under
an overhang of less than three (3) feet from the top of
the heater. Three (3) sides must be open in the area
under the overhang. Roof water drainage must be
diverted away from heaters installed under overhangs
with the use of gutters.
WARNING: The heater shall not be located in an
area where water sprinklers, or other devices, may
cause water to spray through the cabinet louvers
and into the heater. This could cause heavy internal
rusting or damage some electrical components, and
this would void the warranty.
Outdoor Heaters (926–
1758)
Heater
Clearance
Side
(Inches)
Top
24
Back
24
Right Side
24
Left Side
24
Fig. 2: Minimum Distance from Openings
The point from where the flue products exit the heater
must be a minimum of four (4) feet below, four (4) feet
horizontally from or one (1) foot above any door, win-
dow or gravity inlet to a building. The top surface of
the heater shall be at least three (3) feet above any
forced air inlet, or intake ducts located within ten (10 )
feet horizontally.
High Wind Conditions
(Outdoor Units Only)
In areas where high winds are frequent, it may be nec-
essary to locate the heater a minimum of 3' from high
vertical walls, or install a wind break so the heater is
not in direct wind current.
Indoor Heaters
The design is certified for indoor installation when
equipped with approved drafthood. Locate the heater
as close as practical to a chimney or gas vent.
Combustion Air
(Indoor Units Only)
The heater must have both combustion and ventila-
tion air. Openings must not be obstructed. Minimum
requirements are from the National Fuel Gas Code
CAUTION:
Combustion
contaminated by corrosive chemical fumes which
can cause unwarrantable damage to the heater.
6
air
must
not
be

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents