Low Water Cutoff
Automatically shuts down burner whenever water
level drops below probe. A 3 to 5 second time delay
prevents premature lockout due to temporary condi-
tions such as power failure or air pockets. Standard
on Cal Code heaters.
Fig. 25: Low Water Cutoff
High & Low Gas Pressure Switches
Pressure switches sense either high or low gas pres-
sure and automatically shut down burners if abnormal
pressures exist. Standard on Models 3001-4001.
Fig. 26: High/Low Gas Pressure Switch

Electrical Wiring

DANGER - SHOCK HAZARD - Make sure
electrical power to the heater is disconnected to avoid
potential serious injury or damage to components.
CAUTION: Label all wires prior to disconnection
when servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper
operation after servicing.
NOTE: If it is necessary to replace any of the
original wiring, it must be replaced with 105° C wire
or its equivalent.
NOTE: Models 2100-4001 require 240VAC power
to the pump.
Electronic Ignition
The intermittent ignition device conserves energy by
automatically extinguishing the pilot when desired
temperature is reached. When additional heat is need-
ed, the pilot re-ignites electrically, eliminating the fuel
costs of maintaining a constant pilot. To ensure safe
operation, the gas valve cannot open until the pilot
relights and is confirmed.
Heater must be electrically grounded and bonded
Without Lockout
Model
N
926–1826
Standard
2100–4001
N/A
Table E: Lockout Availability
in accordance with local codes, or, in the absence
of local codes, with the latest edition of the National
Electrical Code, ANSI/NFPA 70.
The heater draws less than 1 amp - not includ-
ing the pump power - when operating on either
120VAC or 240VAC power.
Fig. 27: Ignition Module
19
With Lockout
P
N
P
N/A
Optional
Standard
N/A
Standard
Standard