Section 4 / Servicing Instructions; General Location Of Controls; Control Adjustments / Replacements; Pressure Switch - Raypak Versa 105B Brass Installation And Operating Instructions Manual

Above ground pool and spa heater
Table of Contents

Advertisement

SECTION 4 / SERVICING INSTRUCTIONS

GENERAL LOCATION OF CONTROLS

HIGH LIMITS
BYPASS
VALVE
THERMAL
FUSE
TRANSFORMER
IGNITION CONTROL (IID)
BURNERS & PILOT
CONTROLS/ADJUSTMENTS/
REPLACEMENTS
TEMPERATURE CONTROLS
The water temperature is controlled by the heater
thermostat on the upper front panel of the heater. The
control center contains an On/Off toggle switch and a
thermostat. The switch functions as a means for turning
the heater on or off.
The thermostat is fitted with a means of limiting the
upper temperature limit below the maximum level. The
knob stop adjustment ring illustrated below is adjust-
able by loosening the set screw, rotating the knobstop
ring to the desired location and retightening the set
screw.
Typical
Comfortable
Spa
Temperature
Range
Knobstop Ring
Typical
Comfortable
Pool
Temperature
Range
Set Screw
Fig# 9252

PRESSURE SWITCH

The pressure switch, or heater actuator, insures
that the heater operates only when the filter pump is in
operation. It is factory set at 1.75 PSI for deck level
installations. When the heater is located below the level
of the spa or pool, it may be necessary to reset the
pressure switch to compensate for the no-flow static
head. If it is necessary to reset the pressure switch, we
recommend the following procedure: see next page
please.
21
MANUAL
THERMOSTAT
MANUAL
SWITCH
PRESSURE
SWITCH
GAS VALVE