Haes Excel-EN Installation, Commissioning & Operating Manual page 27

En54 approved 2 - 12 zone conventional control panel
Table of Contents

Advertisement

Set Fault Buzzer Volume
2
2
2
4
There are two levels of volume for the internal fault buzzer, high and low.
Enter the above code and press the ENTER button to increase or decrease
the fault buzzer tone from the previous level.
Setting will change when ENTER button is pressed.
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to 'OFF'.
Clear All Disablements
1
1
2
1
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
Any disabled zone, sounder circuit, output or delay will now be enabled.
The panel will bleep to acknowledge the reset.
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to 'OFF'.
Initialise Factory Default Settings
1
1
1
3
Enter the above code and press the ENTER button.
Then press the ENTER button again and hold for 3 seconds.
All disablements, test modes and programming will revert back to the
factory default settings.
The panel will bleep to acknowledge the reset.
When fi nished, enter the next programming code or disable the controls and return DIL switch 6 to 'OFF'.
Excel-EN Installation, Commissioning & Operating Manual
SETUP & PROGRAMMING
Approved Document Ref: UI-XLEN-01 Issue 7.0
25
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
RESOUND
SILENCE
RESET
1
2
3
4
Disable
Test
Mute
Test
Mode
Mode
Buzzer
Lamps
ENTER
ENTER
ENTER