General Specifi cation
Enclosure
Cabling
Temperature range
Number of conventional/Twin Wire detection circuits
Conventional/Twin Wire detector compatibility
POWER SUPPLY MODULE
Power Supply Specifi cation
Mains supply
Mains supply fuse
Internal power supply rating
Power supply output voltage
Maximum continuous load for battery
standby (ImaxA)
Minimum current drawn by panel
(example)
Maximum ripple
Min/max battery size and type
Battery charging voltage
Battery charging output current
Battery high impedance fault (Batt Hi Z)
Max current drawn from batteries
Excel-EN Installation, Commissioning & Operating Manual
Steel IP30. Epoxy powder coated Interpon Radon, silver grey
Fire resistant screened cable, minimum size 1mm
1Km (20 Ohm). FireBurn, FP200 or equivalent (max capacitance 1uF,
max inductance 1 millihenry).
-5 deg C to +40 deg C max RH 95%
2 - 12
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
230vac +10% / -15% 50Hz max current
1.2A
4 Amp (F4A 250V)
3.0 Amps total including battery charging
21.27 - 29.68vdc
ImaxA = 610mA
4 Zone
I min = 90mA
120 mV p-p
2 x 7.0Ah 12volt VRLA
Use Yuasa NP range batteries
27.3 vdc nominal at 20 deg C
3.0A PSU 1.34A
Current limited 4.7 Ohms
Resistance > 1 Ohm
3.15 Amps with main power source
disconnected. Battery fuse 3.15A LBC
20mm.
9
ABOUT THIS PANEL
. Max cable length
2
Not accessible for servicing. Internal to
switch mode power unit
Maximum load shared between outputs
= 2.4A
Tolerance +/- 0.1%
ImaxB not specifi ed
12 Zone
I min = 188mA
Supply and charger fault monitored
Other equivalent batteries may be
used but have not been tested for the
purposes of EN54 approval.
Temperature compensated
1 hour reporting time
Approved Document Ref: UI-XLEN-01 Issue 7.0