5580/5380 Controllers
Data Type Size - 32 bytes
5580/5380 controllers
Word
Elements
Data Type
0
My_DINT
DINT
1
Padding Bytes
2
Large_Value
LINT
3
4
Big_Value
DINT
5
Float_Value
REAL
6
Small_Value
INT, SINT, BOOL,
Tiny_Value, Bit 1
BOOL
Bit_2
7
Padding Bytes
This implementation affects UDTs that contain LINT data types, including
LINTs that are in nested UDTs.
- 64-Bit Boundary
Mapping Table (8 bits each column
MAP
MAP
MAP
MAP
PAD
PAD
PAD
PAD
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
PAD
PAD
PAD
PAD
Mitigation
See
Produce and Consume Tags on page
UDTs between the following:
• 5580 and 5570 controllers that use Logix Designer projects, version 26
or earlier
• 5380 and 5370 controllers that use Logix Designer projects, version 26
or earlier
For more information about mapping, see
If you use COP or CPS instructions to move data between UDT-based tags
and simple arrays, review your logic. Make sure that the COP/CPS
instructions are the correct length, and the logic matches the position of the
data within the array.
For example, when you use a CPS instruction to copy a SINT[32] array that is
obtained from an external device into a UDT that contains LINTs
Rockwell Automation Publication 1756-RM100F-EN-P - October 2018
5570/5370 Controllers
Data Type Size - 24 bytes
Word
Elements
5570/5370 controllers - 32 Bit Boundary
Data Type
0
My_DINT
DINT
1
Large_Value
LINT
2
3
Big_Value
DINT
4
Float_Value
REAL
5
Small_Value
INT, SINT,
BOOL,
Tiny_Value, Bit 1
BOOL
Bit_2
96, if you Produce/Consume tags in
Data Structures on page
Instruction Execution
Chapter 6
Mapping Table (8 bits each column
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
MAP
97.