Outdoor Unit
2.5

Removal of Four Way Valve

Procedure
Step
1. Remove the peripheries.
Remove the four
way valve and the
sheets of putty so as
not to burn them.
1
Remove the terminal
cover.
2
Loosen the screw of the
four way valve coil.
172
Warning
Be sure to wait 10 minutes or more after turning off all power supplies
before disassembling work.
Procedure
Terminal
cover
Red (U)
Yellow(V)
Be careful so as not to burn
(R3276)
the compressor terminals or
the name plate.
Make a note.
Blue (W)
(R3277)
SiEBE04-507