Daikin D Series Service Manual page 115

Inverter pair wall mounted type, cooling only, heat pump
Hide thumbs Also See for D Series:
Table of Contents

Advertisement

SiEBE04-507
Troubleshooting
Check No.4
Refer to P.120
Check No.6
Refer to P.122
Check No.7
Refer to P.123
Check No.9
Refer to P.124
Service Diagnosis
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Check the installation space.
Check No.7
Installation condition
check
Normal
Check No.9
Outdoor fan check
Normal
Check No.4
Electronic expansion valve check
Judgment
Normal
Check No.6
Heat exchanger thermistor check
Judgment
Normal
Abnormal
Abnormal
Abnormal
Abnormal
Troubleshooting
Change the air outlet grille
position.
Change the installation
location.
Clean the heat exchanger.
Replace the fan motor.
Repair the connector or fan
motor lead wires.
Replace the electronic
expansion valve or coil.
Replace the PCB.
Replace the heat exchanger
thermistor.
Replace PCB.
(R2 8 55)
105