Output And Input Data - Danfoss VLT Soft Starter MCD 600 Installation Manual

Devicenet card
Hide thumbs Also See for VLT Soft Starter MCD 600:
Table of Contents

Advertisement

Installation Guide | DeviceNet Card

3.4.1 Output and Input Data

Table 2: Master/Slave Polled I/O Output Data Structure
Byte
Bit
0
0
1
2
3–7
1
0–1
2–7
Table 3: Master/Slave Polled I/O Input Data Structure
Byte
Bit
Function
0
0
Trip
1
Warning
2
Running
3
Reserved
4
Ready
5
Operating mode
6
Command source
7
At reference
Danfoss A/S © 2018.10
Function
0=Stop command
1=Start command
0=Enable start or stop command
1=Quick stop (coast to stop) and disable start command
0=Enable start or stop command
1=Reset command and disable start command
Reserved
0=Use soft starter remote input to select motor set
1=Use primary motor set when starting
2=Use secondary motor set when starting
3=Reserved
Reserved
Value
1=Tripped
1=Warning
0=Unknown, Not ready, Ready to start, or Tripped
1=Starting, Running, Stopping, or Jogging
0=Start or stop command not acceptable
1=Start or stop command acceptable
0=Programming mode
1=Operating mode
0=Remote LCP, Digital input, Clock
1=Network
1=Running
Configuration
AQ277154750780en-000102 / 175R1182 | 9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents