Bindicator SonoTracker Ultrasonic Liquid Level Installation & Operation Manual page 50

Can monitor up to a total of 8 transducers of various frequencies, accommodating multiple vessels of different heights and shapes.
Table of Contents

Advertisement

Press the arrow keys to access the options of the Weir Menu. Press Enter for your desired options. Once
completed, you will go to Step 9, Select Flow Type.
8. Nozzle—The only option here is Ken. Press ENTER.
Primary Element
Ken
ENTER.9.
by scrolling through the options with the arrow keys. Press ENTER.
Select Flow Type
* CFS
10. The Flow Format allows you to choose how many digits you want to the left and right of the decimal
point for displaying the flow rate. Scroll through the format options and press ENTER.
Pick Flow Format
* XXX.XX
Note: Weir: If you selected Other in the Menu, the controller asks you to enter a custom value for Crest Length.
Use the keypad to enter the Crest Length. Press the Enter Key. The display flashes a message acknowledging
your selection. Go to Step 9.
Note: CFS is cubic feet per second, GPS is gallons per second, GPM is gallons per minute, GPD is gallons per
day, and MGD is million gallons per day.
11. After selecting Flow Format, the display prompts you to select the Total Type, the units to use for
measuring total flow. The display shows:
Total Type
* CF
An asterisk indicates the default units. CF is cubic feet, GL is gallons, and MG is million gallons.
12. After selecting the Total Type, the display prompts you to select the Total Format or Totalizer Format.
This allows you to select how many digits you want to the left and right of the decimal point or how
many fixed zeros you want for displaying the total flow. The display shows:
Total Format
XXX000
13. Use the arrow keys to scroll through the options available. Press ENTER. The display shows:
Zero Calibration
Auto
The SonoTracker Series controller has two methods of calibration, Auto and Manual, for a flow
application. For Auto calibration, you enter the maximum head and the current head. For Manual
calibration, you enter the maximum head and the zero distance. Press ENTER to select Auto or the arrow
key to select Manual, then ENTER. If you select Manual, skip Step 15 and go directly to Step 16 to
calculate Zero Distance.
Scroll through the Kennison Nozzle options with the arrow keys and press
Flow Type determines the units to use for measuring the flow rate. Select the Flow Type
46
www.bindicator.com
SON280020 Rev. C